Short description
Bus transmitter X2X Link bus transmitter with supply for I/O
General information
B&R ID code 0xE219
Status indicators X2X bus function, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
X2X bus function Yes, using LED status indicator
Power consumption
Bus 0.5 W
Internal I/O
As bus transmitter 0.1 W
Additionally as supply module 0.6 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
Input I/O power supply
Input voltage 24 VDC -15% / +20%
Fuse Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection No
Output I/O power supply
Nominal output voltage 24 VDC
Behavior on short circuit Required line fuse
Permissible contact load 10 A
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Starting temperature Yes, -40°C
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Up to 100%, condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB06 or X20TB12 separately.
Order 1x bus module X20cBM11 separately.
Pitch 12.5+0.2 mm
Malzeme numarası:
X20cBT9100
Açıklama:
  • X2X Link bus transmitter
  • For seamless expansion of the system
  • Up to 100 m segment length
  • Supply for internal I/O power supply
  • Operation only on the rightmost slot

The bus transmitter is used for seamless expansion of the X20 system. Stations can be up to 100 m apart.

The bus transmitter module is only permitted to be operated with a bus module where the internal I/O power supply is connected through (e.g. X20BM11).

If the supply is used for the internal I/O power supply, this potential group is not permitted to be supplied by any other module. An I/O module with bus module X20BM01 must be used to isolate the potential group.

Zorunlu aksesuarlar
Bus modules
X20cBM11 X20 bus module, coated, 24 VDC keyed, internal I/O power supply connected through
Terminal blocks
X20TB06 X20 terminal block, 6-pin, 24 VDC keyed
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
İsteğe bağlı aksesuarlar
X2X Link cable
X67CA0X99.1000 Cable for custom assembly, 100 m
X67CA0X99.5000 Cable for custom assembly, 500 m
Automation Studio donanım yükseltmeleri Sürüm (Tarih) İndirme
V3.0 HW Upgrade (X20cBT9100) EXE / 2 MB
V4.0 HW Upgrade (X20cBT9100) EXE / 888 KB
Dökümantasyon Sürüm (Tarih) İndirme
Coated modules PDF / 62 KB
Data sheet X20(c)BT9100 PDF / 476 KB
Installation- / EMC-Guide PDF / 20 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Elektro veya EPLAN şablonları) Sürüm (Tarih) İndirme
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. Şablonlar) Sürüm (Tarih) İndirme
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB
Sertifikalar Sürüm (Tarih) İndirme
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
UK Declaration PLC X20 PDF / 151 KB

Lütfen ülke ve dil seçin

B&R Logo