DWL@DWL10000303029

Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.13.0.0 * 2024-12-11 3 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP3586

Version 1.13.0.0:

ID: QCAS-1019
POWERLINK: Lockup of MN operating 3rd party CN devices
Unsynchronized frame reception in the MN caused by 3rd party CN blocked thecommunication.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\1538_0.pci(19), 1\1538a0.epl(143)

Version 1.2.0.0:

ID:772265
Wrong power consumption data corrected: calculated values in AS did not match to correct documentation
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\1538_0.pci(17), 1\1538a0.epl(141)

Version 1.1.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.0.0.0:

ID: 691650
Support PLCCP3585
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\1538_0.pci(17), 1\1538a0.epl(141)
Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.11.0.0 * 2023-07-20 3 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP3586

Version 1.11.0.0:

ID: 772685 / Support ID: 400400350, 400406359, 400407650
Wrong power consumption data corrected: calculated values in AS did not match to correct documentation
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(142)

Version 1.10.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.9.0.1:

ID: 709895
Test
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(142)

Version 1.9.0.0:

ID: 691740 / Support ID: 400325418
POWERLINK: Operating mode "Ethernet"
If a POWERLINK interface was operated in operating mode "Ethernet" and connected to a POWERLINK network in this mode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(142)

Version 1.8.1.0:

ID: 664845
Support data point StorageWear, wear level of storage medium starting fromAR A4.90
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 694590
Support for automatic DNA configuration fromAS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(141)

Version 1.8.0.0:

ID: 652280
POWERLINK: Possible failure of already configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652445
Error correction: DNA tree topologies not always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(141)

Version 1.6.0.0:

ID: 635430
Module documentation revised
Data sheet V1.52
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635555
POWERLINK-Manager: With frequent failure of CN's, which are operated with the optimization "Chainedstation" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(138)

Version 1.5.0.0:

ID: 542445
Changing the position of "Temperature data type configuration" in the CPU configuration
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 590110
X20CPx58x: I/O Datapoints "SupplyVoltage" and "SupplyCurrent" for onboard PS module
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 590125
Module documentation revised
Data sheet V1.39
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603380 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(136)

Version 1.4.2.0:

ID: 539065 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature displayrange
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.3.0.0:

ID: 462635
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462670
Update online help
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 462740 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462830 / SupportID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.2.0.0:

ID: 443670 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes

ID: 445155
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(15), 1\57886a0.epl(128)

Version 1.1.0.0:

ID: 417210
Enhancement ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 417285
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417350
Documentation: enhancements and corrections
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 417475
Optimized EMC characteristics for GL
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes

ID: 423955 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter,the dropping out of an SoC sometimes caused a permanent freezing of the inputdata on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424055/ Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(15), 1\57886a0.epl(127)

Version 1.0.1.1:

ID: 391700 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(13), 1\57886a0.epl(123)

Version 1.0.1.0:

ID: 391235 / Support ID: 0
Sporadic error when starting the onboard POWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(13), 1\57886a0.epl(123)

Version 1.0.0.1:

ID: 341970
Support X20cCP3586
Enhancement online-help
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(12), 1\57886a0.epl(123)

Version 1.0.0.0:

ID: 341970
Support X20cCP3586
Firstversion
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(11), 1\57886a0.epl(121)
Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.10.0.0 * 2021-07-23 2 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP3586

Version 1.10.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.9.0.1:

ID: 709895
Test
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(142)

Version 1.9.0.0:

ID: 691740 / Support ID: 400325418
POWERLINK: Operating mode "Ethernet"
If a POWERLINK interface was operatedin operating mode "Ethernet" and connected to a POWERLINK network in this mode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(142)

Version 1.8.1.0:

ID: 664845
Support data point StorageWear, wear level of storage medium starting fromAR A4.90
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 694590
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(141)

Version 1.8.0.0:

ID: 652280
POWERLINK: Possible failure of already configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652445
Error correction: DNA tree topologies not always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(141)

Version 1.6.0.0:

ID: 635430
Module documentation revised
Data sheet V1.52
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635555
POWERLINK-Manager: With frequent failure of CN's, which are operatedwith the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(138)

Version 1.5.0.0:

ID:542445
Changing the position of "Temperature data type configuration" inthe CPU configuration
Channel description changed: No
Configurationdescription changed: Yes
Firmware changed: No

ID: 590110
X20CPx58x: I/O Datapoints "SupplyVoltage" and "SupplyCurrent" for onboard PS module
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 590125
Module documentation revised
Data sheet V1.39
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603380 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization:Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(136)

Version 1.4.2.0:

ID: 539065 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature display range
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.3.0.0:

ID: 462635
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462670
Update online help
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 462740 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462830 / Support ID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.2.0.0:

ID: 443670 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 445155
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(15), 1\57886a0.epl(128)

Version 1.1.0.0:

ID: 417210
Enhancement ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 417285
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417350
Documentation: enhancements and corrections
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 417475
Optimized EMC characteristics for GL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 423955 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424055 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled nodesometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(15), 1\57886a0.epl(127)

Version 1.0.1.1:

ID: 391700 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(13), 1\57886a0.epl(123)

Version 1.0.1.0:

ID: 391235 / Support ID: 0
Sporadic error when starting the onboard POWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(13), 1\57886a0.epl(123)

Version 1.0.0.1:

ID: 341970
Support X20cCP3586
Enhancement online-help
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(12), 1\57886a0.epl(123)

Version 1.0.0.0:

ID: 341970
Support X20cCP3586
First version
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(11), 1\57886a0.epl(121)
Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.9.0.0 * 2020-11-04 2 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP1584

Version 1.9.0.0:

ID: 691740 / Support ID: 400325418
POWERLINK: Operating mode "Ethernet"
If a POWERLINK interface was operated in operatingmode "Ethernet" and connected to a POWERLINK network in this mode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17),1\57883a0.epl(142)

Version 1.8.1.0:

ID: 664845
Support data point StorageWear, wear level of storage medium starting fromAR A4.90
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 694590
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(141)

Version 1.8.0.0:

ID: 652280
POWERLINK: Possible failure of already configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652445
Error correction: DNA tree topologies not always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(141)

Version 1.6.0.0:

ID: 635430
Module documentation revised
Data sheet V1.52
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635555
POWERLINK-Manager: With frequent failure of CN's, which are operated with the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(138)

Version 1.5.0.0:

ID: 542445
Changing the position of "Temperature data type configuration" in the CPU configuration
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 590110
X20CPx58x: I/ODatapoints "SupplyVoltage" and "SupplyCurrent" for onboard PSmodule
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 590125
Module documentation revised
Data sheet V1.39
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603380 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically presentin the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(136)

Version 1.4.2.0:

ID: 537770 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature display range
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.0.0:

ID: 462620
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462640
Update online help
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 462725 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462805 / Support ID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.2.0.0:

ID: 443655 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 445140
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(128)

Version 1.1.0.0:

ID: 417225
Enhancement ECAD data
Channeldescription changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 417310
Support Bonding feature
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417365
Documentation: enhancements and corrections
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 417495
Optimized EMC characteristics for GL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 423920 / SupportID: 400138730
POWERLINK V2: "Controlled node" mode
In networks withheavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424035 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(127)

Version 1.0.1.1:

ID: 391690 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.1.0:

ID: 388285 / Support ID: 0
Sporadic error when starting the onboard POWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.0.1:

ID: 311570
Support X20cCP1584
Enhancement online-help
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(12), 1\57883a0.epl(123)

Version 1.0.0.0:

ID: 311570
Support X20cCP1584
First version
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(11), 1\57883a0.epl(121)
Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.8.1.0 * 2020-08-20 2 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP1584

Version 1.8.1.0:

ID: 664845
Support data point StorageWear, wear level of storage medium starting fromAR A4.90
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 694590
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(141)

Version 1.8.0.0:

ID: 652280
POWERLINK: Possible failure of already configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652445
Error correction: DNA tree topologies not always started up correctly
Channel description changed:No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(141)

Version 1.6.0.0:

ID: 635430
Module documentation revised
Data sheet V1.52
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635555
POWERLINK-Manager: With frequentfailure of CN's, which are operated with the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(138)

Version 1.5.0.0:

ID: 542445
Changing the position of "Temperature data type configuration" in the CPU configuration
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 590110
X20CPx58x: I/O Datapoints "SupplyVoltage" and "SupplyCurrent" for onboard PS module
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 590125
Module documentation revised
Data sheet V1.39
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603380 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(136)

Version 1.4.2.0:

ID: 537770 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature display range
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.0.0:

ID: 462620
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462640
Update online help
Channel description changed:No
Configuration description changed: No
Firmware changed: No

ID: 462725 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462805 / Support ID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.2.0.0:

ID: 443655 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 445140
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(128)

Version 1.1.0.0:

ID: 417225
Enhancement ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID:417310
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID:417365
Documentation: enhancements and corrections
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 417495
Optimized EMC characteristics for GL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 423920 / Support ID: 400138730
POWERLINKV2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424035 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINKmanager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(127)

Version 1.0.1.1:

ID: 391690 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.1.0:

ID: 388285 / Support ID: 0
Sporadic error when starting the onboard POWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.0.1:

ID: 311570
Support X20cCP1584
Enhancement online-help
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes
Firmware: 1\57883_0.pci(12), 1\57883a0.epl(123)

Version 1.0.0.0:

ID: 311570
Support X20cCP1584
First version
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(11), 1\57883a0.epl(121)
Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.8.0.0 * 2019-12-12 2 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP1584

Version 1.8.0.0:

ID: 652280
POWERLINK: Possible failure of alreadyconfigured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652445
Error correction: DNA tree topologiesnot always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(141)

Version 1.6.0.0:

ID: 635430
Module documentation revised
Data sheet V1.52
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635555
POWERLINK-Manager: With frequent failure of CN's, which are operated with the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(138)

Version 1.5.0.0:

ID: 542445
Changing the position of "Temperature data type configuration" in the CPU configuration
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 590110
X20CPx58x: I/O Datapoints "SupplyVoltage" and "SupplyCurrent" for onboard PS module
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 590125
Module documentation revised
Data sheet V1.39
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603380 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(136)

Version 1.4.2.0:

ID: 537770 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature display range
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed:No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.0.0:

ID: 462620
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462640
Update online help
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 462725 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462805 / Support ID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.2.0.0:

ID: 443655 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 445140
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(128)

Version 1.1.0.0:

ID: 417225
Enhancement ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 417310
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417365
Documentation: enhancements and corrections
Channel description changed:No
Configuration description changed: No
Firmware changed: No

ID: 417495
Optimized EMC characteristics for GL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 423920 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of anSoC sometimes caused a permanent freezing of the input data on the controllednode.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424035 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(127)

Version 1.0.1.1:

ID: 391690 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.1.0:

ID: 388285 / Support ID: 0
Sporadic error when starting the onboard POWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.0.1:

ID: 311570
Support X20cCP1584
Enhancement online-help
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(12), 1\57883a0.epl(123)

Version 1.0.0.0:

ID: 311570
Support X20cCP1584
First version
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(11), 1\57883a0.epl(121)
Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.6.0.0 * 2019-04-16 2 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP1584

Version 1.6.0.0:

ID: 635430
Module documentation revised
Datasheet V1.52
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635555
POWERLINK-Manager: With frequent failure of CN's, which are operated with the optimization"Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17),1\57883a0.epl(138)

Version 1.5.0.0:

ID: 542445
Changing the position of "Temperature data type configuration" in the CPU configuration
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 590110
X20CPx58x: I/O Datapoints "SupplyVoltage" and "SupplyCurrent" for onboard PS module
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 590125
Module documentation revised
Data sheet V1.39
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603380 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(136)

Version 1.4.2.0:

ID: 537770 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature display range
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel description changed:No
Configuration description changed: No
Firmware changed: No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.0.0:

ID: 462620
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462640
Update online help
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 462725 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462805 / Support ID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.2.0.0:

ID: 443655 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes

ID: 445140
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(128)

Version1.1.0.0:

ID: 417225
Enhancement ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 417310
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417365
Documentation: enhancements and corrections
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 417495
Optimized EMC characteristics for GL
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: Yes

ID: 423920 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424035 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(127)

Version 1.0.1.1:

ID: 391690 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.1.0:

ID: 388285 / Support ID: 0
Sporadic error when starting the onboard POWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version1.0.0.1:

ID: 311570
Support X20cCP1584
Enhancement online-help
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(12), 1\57883a0.epl(123)

Version 1.0.0.0:

ID: 311570
Support X20cCP1584
First version
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(11), 1\57883a0.epl(121)
Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.5.0.0 * 2018-09-07 2 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP1584

Version 1.5.0.0:

ID: 542445
Changing the position of "Temperature data type configuration" in the CPU configuration
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 590110
X20CPx58x: I/O Datapoints "SupplyVoltage" and "SupplyCurrent" for onboard PS module
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 590125
Module documentation revised
Data sheet V1.39
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603380 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(136)

Version 1.4.2.0:

ID: 537770 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature display range
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration descriptionchanged: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.3.0.0:

ID: 462620
IP packets withmulticast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462640
Update online help
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 462725 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462805 / Support ID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(17), 1\57883a0.epl(129)

Version 1.2.0.0:

ID: 443655 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 445140
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(128)

Version 1.1.0.0:

ID: 417225
Enhancement ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 417310
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417365
Documentation: enhancements and corrections
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 417495
Optimized EMC characteristics for GL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 423920 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out ofan SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424035 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configurationdescription changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(15), 1\57883a0.epl(127)

Version 1.0.1.1:

ID: 391690 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.1.0:

ID: 388285 / Support ID: 0
Sporadic error when starting the onboardPOWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57883_0.pci(13), 1\57883a0.epl(123)

Version 1.0.0.1:

ID: 311570
Support X20cCP1584
Enhancement online-help
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes
Firmware: 1\57883_0.pci(12), 1\57883a0.epl(123)

Version 1.0.0.0:

ID: 311570
Support X20cCP1584
First version
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57883_0.pci(11), 1\57883a0.epl(121)
Version Språk
Operativ system
Datum
Storlek
Typ Ladda ner
1.4.2.0 * 2017-06-09 2 MB EXE AS4_HW_X20cCP3586.exe
Beskrivning V4.0 HW Upgrade (X20cCP3586)

Revision information X20cCP3586

Version 1.4.2.0:

ID: 539065 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timingproblem in the firmware it could happen that no asynchronous frames were sentin the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature display range
Channel descriptionchanged: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.3.0.0:

ID: 462635
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462670
Update online help
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 462740 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462830 / Support ID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(17), 1\57886a0.epl(129)

Version 1.2.0.0:

ID: 443670 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configurationdescription changed: No
Firmware changed: Yes

ID: 445155
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(15), 1\57886a0.epl(128)

Version 1.1.0.0:

ID: 417210
Enhancement ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 417285
SupportBonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417350
Documentation: enhancements and corrections
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 417475
Optimized EMC characteristics for GL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 423955 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424055 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, thecontrolled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(15), 1\57886a0.epl(127)

Version 1.0.1.1:

ID: 391700 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57886_0.pci(13), 1\57886a0.epl(123)

Version 1.0.1.0:

ID: 391235 / Support ID: 0
Sporadic error when starting the onboard POWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(13), 1\57886a0.epl(123)

Version 1.0.0.1:

ID: 341970
Support X20cCP3586
Enhancement online-help
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57886_0.pci(12), 1\57886a0.epl(123)

Version 1.0.0.0:

ID: 341970
Support X20cCP3586
First version
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57886_0.pci(11), 1\57886a0.epl(121)