Short description
Bus controller DeviceNet adapter
General information
Inputs/Outputs 8 digital channels, configurable as inputs or outputs using software, inputs with additional functions
Insulation voltage between channel and bus 500 Veff
Nominal voltage 24 VDC
B&R ID code
Bus controller 0x17D5
Internal I/O module 0x1311
Sensor/Actuator power supply 0.5 A summation current
Status indicators I/O function per channel, supply voltage, bus function
Diagnostics
24 V DeviceNet voltage Yes, using LED status indicators (MOD and NET)
Outputs Yes, using LED status indicator and software
I/O power supply Yes, using LED status indicator and software
Connection type
Fieldbus M12, A-coded
X2X Link M12, B-coded
Inputs/Outputs 8x M8, 3-pin
I/O power supply M8, 4-pin
Power output 3 W X2X Link power supply for I/O modules
Power consumption
Fieldbus 2.7 W
Internal I/O 2 W
X2X Link power supply 6.6 W at maximum power output for connected I/O modules
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
Interfaces
Fieldbus DeviceNet adapter
Variant M12 interface (male connector on the module)
Max. distance 500 m
Transfer rate Max. 500 kbit/s
Default transfer rate Automatic transfer rate detection
Min. cycle time
Fieldbus No limitation
X2X Link 400 μs
Synchronization between bus systems possible No
Terminating resistor Can be optionally screwed onto the Y-connector
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Power consumption
Sensor/Actuator power supply Max. 12 W
Sensor/Actuator power supply
Voltage I/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 A Max. 2 VDC
Summation current Max. 0.5 A
Short-circuit proof Yes
Digital inputs
Input characteristics per EN 61131-2 Type 1
Input voltage 18 to 30 VDC
Input current at 24 VDC Typ. 4 mA
Input circuit Sink
Input filter
Hardware ≤10 μs (channels 1 to 4) / ≤70 µs (channels 5 to 8)
Software Default 0 ms, configurable between 0 and 25 ms in 0.2 ms intervals
Input resistance Typ. 6 kΩ
Additional functions 50 kHz event counting, gate measurement
Switching threshold
Low <5 VDC
High >15 VDC
Event counters
Quantity 2
Signal form Square wave pulse
Evaluation Each negative edge, cyclic counter
Input frequency Max. 50 kHz
Counter 1 Input 1
Counter 2 Input 3
Counter frequency Max. 50 kHz
Counter size 16-bit
Gate time measurement
Quantity 1
Signal form Square wave pulse
Evaluation Positive edge - Negative edge
Counter frequency
Internal 48 MHz, 3 MHz, 187.5 kHz
Counter size 16-bit
Length of pause between pulses ≥100 µs
Pulse length ≥20 µs
Supported inputs Input 2 or input 4
Digital outputs
Variant Current-sourcing FET
Switching voltage I/O power supply minus residual voltage
Nominal output current 0.5 A
Total nominal current 4 A
Output circuit Source
Output protection Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply
Diagnostic status Output monitoring with 10 ms delay
Leakage current when the output is switched off 5 µA
Switching on after overload shutdown Approx. 10 ms (depends on the module temperature)
Residual voltage <0.3 V at 0.5 A nominal current
Peak short-circuit current <12 A
Switching delay
0 → 1 <400 µs
1 → 0 <400 µs
Switching frequency
Resistive load Max. 100 Hz
Inductive load See section "Switching inductive loads".
Braking voltage when switching off inductive loads 50 VDC
Electrical properties
Electrical isolation
Channel isolated from DeviceNet and bus

DeviceNet not isolated from bus and channel not isolated from channel
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 200 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Número do material:
X67BC5321
Descrição:
  • Fieldbus: DeviceNet
  • 8 digital channels, configurable as inputs or outputs
  • Simple I/O configuration via the fieldbus
  • Support of both linear and modular (Allen Bradley) configuration systems
  • Auto scan, automatic I/O mapping of the I/Os
  • Automatic I/O configuration
  • Integrated connection to local expansion via X2X Link for 39 additional modules (including up to 16 analog modules)
  • 1 ms cycle time for local expansion

DeviceNet was developed by Allen-Bradley as a CAN bus based automation network. It is based on a producer/consumer protocol. From the user's point of view, all data is handled completely separately from the features of the CAN bus (e.g. longer data packets are fragmented automatically by DeviceNet). I/O messages with defined characteristics are used for access.

This bus controller makes it possible to connect X2X Link I/O nodes to DeviceNet. It has automatic transfer rate detection, auto scan, automatic mapping and automatic configuration of the I/O modules. Explicit messaging, change of state, cyclic, polled and bit strobe are supported as transfer modes.

In addition to the standard communication objects, there are also vendor-specific objects used to represent the modular X67 system in the best manner possible. X67 and other modules that are based on X2X Link can be connected to the bus controller.

The entire configuration of this type of modular system is supported by the DeviceNet standard. Allen Bradley developed the modular I/O configuration to simplify the necessary configuration steps. The DeviceNet bus controllers from B&R also support this type of configuration.

With multifunction modules, the bus controller supports only the default function model in the event of automatic configuration by the bus controller (see the respective module description).

Arquivo com descritivo do equipamento de campo Version (Data) Download
X67BC5321 EDS Package ZIP / 244 KB
Certificados Version (Data) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X67 PDF / 155 KB
TÜV 05 ATEX 7201 X PDF / 5 MB
X20, X67 KC certificates PDF / 6 MB
Documentação Version (Data) Download
Datasheet X67BC5321 PDF / 562 KB
Installation- / EMC-Guide PDF / 20 MB
X67 System User´s Manual PDF / 6 MB
E-CAD (Modelos Electro ou EPLAN) Version (Data) Download
X67 EPLAN P8 from V2.4 EXE / 105 MB
M-CAD (Mechan. Modelos) Version (Data) Download
3D File DXF/STEP X67 ZIP / 1 MB

Por favor escolha o país e o idioma

B&R Logo