3IF787.9-1

Short description
Communication module 1x CAN bus, 1x POWERLINK (V1/V2) managing or controlled node
General information
Status indicators Transmitting/Receiving data for IF1
Status of POWERLINK station, network activity, link/collision for IF2
Diagnostics
Bus function (IF2) Yes, using LED status indicator and software
Data transfer (IF1) Yes, using LED status indicator and software
Station status (IF2) Yes, using LED status indicator and software
Power consumption
3.3 VDC 2.5 W
5 VDC 0.5 W
Total 3.0 W
Electrical isolation
IF1 - IF2 Yes
PLC - IFx Yes
Certifications
CE Yes
UKCA Yes
HazLoc cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD
EAC Yes
KC Yes
Interfaces
Interface IF1
Signal CAN bus
Variant 4-pin male multipoint connector
Max. distance 1000 m
Transfer rate Max. 500 kbit/s
Interface IF2
Fieldbus POWERLINK (V1/V2) managing or controlled node
Type Type 3
Variant 1x shielded RJ45 port
Line length Max. 100 m between two stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex No
Autonegotiation Yes
Auto-MDI/MDIX Yes
Operating conditions
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation 0 to 60°C
Storage -25 to 70°C
Relative humidity
Operation 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block TB704 separately.
Slot Slot, e.g. in the CP360
Número do material:
3IF787.9-1
Descrição:
  • Interface module with CAN bus and POWERLINK
aPCI interface module, 1 POWERLINK interface, managing or controlled node 1 CAN bus interface, electrically isolated, network-capable, max. 500 kbit/s, object buffer in transmit and receive directions, order 1x terminal block TB704 separately!
Acessórios obrigatórios
Terminal blocks
0TB704.9 Accessory terminal block, 4-pin, screw clamp terminal block 2.5 mm²
0TB704.91 Accessory terminal block, 4-pin, push-in terminal block 2.5 mm²
Acessórios opcionais
Infrastructure components
0AC913.93 Bus adapter, CAN bus, 2 CAN bus interfaces, including 03 m attachment cable (TB704)