Short description
| Interfaces | POWERLINK |
| System module | CPU |
General information
Safety characteristics
| Note | See section "Safety characteristics". |
Input SL / BC / X2X Link power supply
| Input voltage | 24 VDC -15% / +20% |
| Input current | Max. 0.9 A |
| Fuse | Integrated, cannot be replaced |
| Reverse polarity protection | No |
Output SL / BC / X2X Link power supply
Input I/O power supply
| Input voltage | 24 VDC -15% / +20% |
| Fuse | Required line fuse: Max. 10 A slow-blow |
| Reverse polarity protection | No |
Output I/O power supply
| Nominal output voltage | 24 VDC |
| Behavior on short circuit | Required line fuse |
| Permissible contact load | 10 A |
Interfaces
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level |
0 to 2000 m: No limitation 2000 to 4000 m: Reduction of the ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature | |
| Operation | |
| Horizontal mounting orientation | 0 to 60°C |
| Vertical mounting orientation | 0 to 50°C |
| Derating | See section "Derating". |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note |
X20 end cover plate (right) included in delivery 12-pin X20 terminal block, safety-keyed, included in delivery |
| Dimensions | |
| Width | 62.5+0.2 mm |
| Height | 99 mm |
| Depth | 75 mm |
| Weight | 198 g |
Materiaalnummer:
X20SL8201Omschrijving:
X20 SafeLOGIC controller, Gen.3 (Safety+) openSAFETY gateway, 1 POWERLINK interface, controlled node, integrated 2-port hub, with X20 bus controller, including power supply module for internal I/O power supply and X2X power supply, 1x terminal block X20TB52 and X20 end cover plate (right) X20AC0SR1 included