Short description
Bus receiver X2X Link bus receiver with supply for I/O and bus
General information
B&R ID code 0xDD48
Status indicators X2X bus function, overload, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Overload Yes, using LED status indicator and software
X2X bus function Yes, using LED status indicator
Power consumption for X2X Link power supply 1.62 W
Power consumption
Internal I/O 0.6 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
X2X Link power supply input
Input voltage 24 VDC -15% / +20%
Input current Max. 0.7 A
Fuse Integrated, cannot be replaced
Reverse polarity protection Yes
X2X Link power supply output
Nominal output power 7 W
Parallel connection Yes
Redundant operation Yes
Overload characteristics Short-circuit proof, temporary overload
Input I/O power supply
Input voltage 24 VDC -15% / +20%
Fuse Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection No
Output I/O power supply
Nominal output voltage 24 VDC
Behavior on short circuit Required line fuse
Permissible contact load 10 A
Electrical properties
Electrical isolation
X2X Link supply isolated from X2X Link power supply

I/O supply not isolated from I/O power supply
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating See section "Derating".
Starting temperature Yes, -40°C
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Up to 100%, condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply bus module X20cBM01 separately
Pitch 12.5+0.2 mm
Materiaalnummer:
X20cBR9300
Omschrijving:
  • X2X Link bus receiver
  • Feed for X2X Link and internal I/O supply
  • Electrical isolation of feed and X2X Link supply
  • Redundancy of X2X Link supply possible by operating multiple supply modules simultaneously
  • Operation only on the slot to the far left

The bus receiver is used to connect the X20 System to the X2X Link. The module is equipped with a feed for the X2X Link as well as the internal I/O supply.

Vereiste toebehoren
Bus modules
X20cBM01 X20 power supply bus module, coated, 24 VDC keyed, internal I/O power supply interrupted to the left
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Optionele toebehoren
X2X Link cable
X67CA0X99.1000 Cable for custom assembly, 100 m
X67CA0X99.5000 Cable for custom assembly, 500 m
Automation Studio HW Upgrades Versie (Datum) Download
V3.0 HW Upgrade (X20cBR9300) EXE / 1 MB
V4.0 HW Upgrade (X20cBR9300) EXE / 676 KB
Certificaten Versie (Datum) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
UK Declaration PLC X20 PDF / 151 KB
Documentatie Versie (Datum) Download
Coated modules PDF / 62 KB
Datasheet X20(c)BR9300 PDF / 396 KB
Installation- / EMC-Guide PDF / 20 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Electro of EPLAN Templates) Versie (Datum) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. Templates) Versie (Datum) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Graag land en taal kiezen

B&R Logo