Short description
Bus receiver | CAN I/O slave |
General information
X2X Link and I/O power supply
Input voltage | 24 VDC -15% / +20% |
Fuse |
Required line fuse: Max. 10 A slow-blow for wiring Integrated fuse for module, non-replaceable |
Reverse polarity protection | Yes |
X2X Link power supply output
Nominal output power | 2 W |
Parallel connection | No |
Redundant operation | No |
Overload characteristics | Short-circuit proof, temporary overload |
Output I/O power supply
Nominal output voltage | 24 VDC |
Behavior on short circuit | Required line fuse |
Permissible contact load | 10 A |
Interfaces
Electrical properties
Electrical isolation |
X2X Link supply not isolated from X2X Link power supply I/O supply not isolated from I/O power supply CAN I/O not isolated from I/O or X2X Link power supply |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB12 separately. Order 1x power supply bus module X20BM01 separately, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included |
Pitch | 12.5+0.2 mm |
Référence produit:
X20BR7300Description:
- Fieldbus: CAN bus
- Automatic firmware update via the fieldbus
- Integrated I/O access in B&R Automation Studio
The bus receiver makes it possible to connect X2X Link I/O nodes to CAN I/O. CAN I/O is a transfer protocol based on standard CAN bus that is fully integrated in the B&R system.
Up to 43 logical I/O modules can be connected to the bus receiver. Up to 16 of these can be analog modules.
Accessoires obligatoires
Bus modules
Terminal blocks
X20TB12 | X20 terminal block, 12-pin, 24 VDC keyed |
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V4.2 HW Upgrade (X20BR7300) | EXE / 1 Mo |
Certifications | Version (date) | Téléchargement |
---|---|---|
EU Declaration ATEX X20 | PDF / 218 Ko | |
EU Declaration of conformity PLC X20 | PDF / 169 Ko | |
UK Declaration PLC X20 | PDF / 151 Ko |
Documentation | Version (date) | Téléchargement |
---|---|---|
Data sheet X20BR7300 | PDF / 274 Ko | |
Installation- / EMC-Guide | PDF / 20 Mo | |
X20 System User´s Manual | PDF / 7 Mo |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 Mo |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 Ko | |
3D File STEP X20 I/O-Slice | ZIP / 872 Ko | |
Dimensions PDF X20 Electronic module | PDF / 3 Ko |