Please choose country and language

Short description
I/O module 8 digital outputs 24 VDC
General information
B&R ID code 0x1467
Status indicators I/O function for each channel, supply voltage, bus function
Diagnostics
Outputs Yes, using status LED and software
I/O power supply Yes, using status LED
Connection type
X2X Link M12, B-keyed
Outputs 8x M8, 3-pin
I/O power supply M8, 4-pin
Power consumption
Internal I/O 2 W
X2X Link power supply 0.75 W
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Power consumption
Actuator power supply Max. 12 W
Digital outputs
Quantity 8
Variant FET positive switching
Nominal voltage 24 VDC
Switching voltage I/O power supply minus residual voltage
Nominal output current 2 A
Total nominal current 8 A
Output circuit Source
Output protection Thermal cutoff for overcurrent and short circuit, integrated protection for switching inductances, reverse polarity protection for output power supply
Actuator power supply 0.5 A summation current
Diagnostic status Output monitoring with 10 ms delay
Leakage current when the power is switched off 5 µA
Switching on after overload shutdown Approx. 10 ms (depends on the module temperature)
Group 1 Channels 1 to 4
Group 2 Channels 5 to 8
Residual voltage <0.5 V at 2 A nominal current
Peak short-circuit current <21 A
Switching delay
0 → 1 <250 µs
1 → 0 <270 µs
Switching frequency
Resistive load Max. 100 Hz
Braking voltage when switching off inductive loads 50 VDC
Continuous current per
Output Max. 2 A
Group Max. 4 A (simultaneity factor = 50%)
Module Max. 8 A
Actuator power supply
Voltage I/O power supply minus voltage drop for short circuit protection
Voltage drop for short-circuit protection at 500 mA Max. 2 VDC
Summation current Max. 0.5 A
Short-circuit proof Yes
Electrical properties
Electrical isolation
Channel isolated from bus

Channel not isolated from channel
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating See section "Derating"
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 180 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Material number:
X67DO1332
Description:
  • 8 A summation current per module
  • All outputs with single-channel diagnostics for short circuit or overload
  • Extremely short cycle times
  • Outputs with short circuit protection
  • Integrated protection for switching inductances

The module is a digital output module for 24 VDC. It has 8 outputs for the source output circuit.

Automation Studio HW Upgrades Version (Date) Download
V2.6 HW Upgrade (X67DO1332F) EXE / 440 KB
V3.0 HW Upgrade (X67DO1332F) EXE / 439 KB
V4.0 HW Upgrade (X67DO1332) EXE / 553 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
E115267 UL CoC X67 PDF / 84 KB
Safe cutoff of potential groups PDF / 147 KB
TÜV 05 ATEX 7201 X PDF / 129 KB
Documentation Version (Date) Download
Datasheet X67DO1332 PDF / 364 KB
X67 System User´s Manual PDF / 19 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X67 EPLAN P8 EXE / 85 MB
X67 EPLAN P8 from V2.4 EXE / 105 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X67 ZIP / 1 MB

Please choose country and language