DWL@DWL10000800514

Version Language
Operating System
Date
Size
Type Download
1.7.0.0 * 10/01/2024 1 MB EXE AS6_HW_X20DO9322.exe
Description V6.0 HW Upgrade (X20DO9322)

Revision information X20DO9322

Version 1.7.0.0:

ID: TDYD-7026
Incorrectly configured modules were not identified on the X2X bus in certain circumstances.
A dynamic hardwareconfiguration is used for various customer applications. In this case, a default configuration is simply created in AS and the actual configuration is readout after the system has started up. Due to a hardware change of several I/O modules, only a cyclic size of 12 bytes (previously 31 bytes) is accepted in the bootloader. If a module with more cyclic data (e.g. a safety module) is nowconfigured, this module can no longer be identified on the bus. As a workaround, these "large" modules can be configured on other X2X slots. This problem can only be corrected with a new bootloader, which can only be delivered via production. Production will be switched to the new software accordingly.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\7066_10.fw(150), 1\7066_11.fw(150), 1\7066_2.fw(561), 1\7066_20.fw(200), 1\7066_21.fw(230), 1\7066_5.fw(801)

Version 1.6.0.0:

ID: 759685
Support new HW variant 21
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\7066_10.fw(150), 1\7066_11.fw(150), 1\7066_2.fw(561), 1\7066_20.fw(200), 1\7066_21.fw(210), 1\7066_5.fw(801)

Version 1.5.0.0:

ID: 738560
Support new HW variant 20
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes
Firmware: 1\7066_10.fw(150), 1\7066_11.fw(150), 1\7066_2.fw(561), 1\7066_20.fw(200), 1\7066_5.fw(801)

Version 1.4.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.3.0.0:

ID: 676525
Support hardware variant 11
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 678820
Module documentation revised
Data sheet V 3.16
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7066_10.fw(150), 1\7066_11.fw(150), 1\7066_2.fw(561), 1\7066_5.fw(801)

Version 1.2.0.0:

ID:
Adaptations for Automation Studio 4.8
Channeldescription changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.1.0.0:

ID: 630155
Support hardware variant 10
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 632195
Module documentation revised
Data sheet V 3.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7066_10.fw(100), 1\7066_2.fw(561), 1\7066_5.fw(801)

Version 1.0.3.0:

ID: 467170
Module documentation revised
Data sheetV 3.12
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7066_2.fw(561), 1\7066_5.fw(801)

Version 1.0.2.2:

ID: 396545
Enhancement online-help files
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7066_2.fw(561), 1\7066_5.fw(801)

Version 1.0.2.1:

ID: 320115
Correction of EPlan export
Adaption pin label for EPlan
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\7066_2.fw(561), 1\7066_5.fw(801)

Version 1.0.2.0:

ID:221375
Increase interference immunity of output status feedbacks
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\7066_2.fw(561), 1\7066_5.fw(801)

Version 1.0.1.0:

ID: 217375
Adaptation UART Re-Init
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\7066_2.fw(560), 1\7066_5.fw(800)
Loading