Short description
Ethernet analysis tool Ethernet analysis tool with up to 2 slots for hub expansion modules
General information
Status indicators Module status, bus function
Diagnostics
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator and software
Power consumption 2 W
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
Interfaces
Type Ethernet analysis tool
Variant 2x shielded RJ45
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex Yes
Autonegotiation Yes
Auto-MDI/MDIX Yes
Electrical properties
Electrical isolation POWERLINK (IF1, IF2) isolated from power supply
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 separately.
Order 1x bus base X20BB8x separately.
Pitch
X20BB80 37.5+0.2 mm
X20BB81 62.5+0.2 mm
X20BB82 87.5+0.2 mm
物料号:
X20ET8819
描述:
  • NetTime time stamp has a resolution of 20 ns
  • Recording and analysis of CRC and frame errors
  • Triggers can also be activated using external digital signals
  • Analysis of both half-duplex and full-duplex networks
  • Able to record two networks simultaneously

POWERLINK has proven itself in the field for years and rarely has problems during commissioning and production. Nonetheless, it is still possible for communication disturbances to occur due to damaged or poor quality cables. If an error occurs, localizing and correcting it is usually very easy thanks to the heterogeneous structure of this flat network type (all data is always visible throughout the network). What's problematic are errors that occur sporadically. This is where tools such as Omnipeek or Wireshark come in.

These tools (or more likely the standard PC technology being used) reach their limits, however, when dealing with machines that have short network cycles. Either not all frames can be recorded, or some telegrams are lost altogether. In these cases, what's needed is a special hardware tool that can work very quickly, record and save every bit of traffic and then pass it on to a laptop.

This module provides different operating modes. For example, it can work passively on the network, in which case the real-time behavior remains unchanged. The device listens in and selectively takes in data when certain defined trigger conditions are met. It can read all of the data, mark it with a timestamp, store it temporarily and ultimately pass it on to a PC. The data is then analyzed in the familiar PC environment.

必备附件
System modules for bus controllers
X20BB80 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20PS9400 X20 power supply module, for bus controller and internal I/O power supply X2X Link power supply
System modules for expandable bus controllers
X20BB81 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, with one expansion slot for X20 add-on module (IF, HB, etc.), X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20BB82 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, with 2 expansion slots for 2 X20 add-on modules (IF, HB, etc.), X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
可选附件
Bus modules
X20BM11 X20 bus module, 24 VDC keyed, internal I/O power supply connected through
X20BM15 X20 bus module, with node number switch, 24 VDC keyed, internal I/O power supply connected through
Digital inputs
X20DI9371 X20 digital input module, 12 inputs, 24 VDC, sink, configurable input filter, 1-wire connections
Digital outputs
X20DO9322 X20 digital output module, 12 outputs, 24 VDC, 0.5 A, source, 1-wire connections
System modules for the X20 hub system
X20HB2880 X20 hub expansion module, integrated 2-port hub, 2x RJ45
X20HB2881 X20 hub expansion module, integrated 2-port hub, for fiber optic cables
E-CAD(电子或EPLAN模板) 版本(日期) 下载
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD(机械模板) 版本(日期) 下载
3D File STEP/DXF X20BC and X20IF Module ZIP / 1 MB
固件升级 版本(日期) 下载
Firmwareupgrade X20ET8819 ZIP / 588 KB
工具/实用程序/ 示例 版本(日期) 下载
B&R Analyzer for Wireshark TM ZIP / 4 MB
Network Analyzer 2 ZIP / 2 MB
文档 版本(日期) 下载
Data sheet X20ET8819 PDF / 965 KB
Installation- / EMC-Guide PDF / 20 MB
X20 System User´s Manual PDF / 7 MB
证书 版本(日期) 下载
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB

请选择国家和语言