General information
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
DNV GL Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
ABS Yes
Terminal block
Number of pins 16
Type of terminal block Push-in terminal
Push-in force per contact Typ. 10 N
Cable type Only copper wires (no aluminum wires!)
Wire stripping length 7 to 9 mm
Connection cross section
Solid wires 0.08 to 1.50 mm² / 28 to 16 AWG
Fine-stranded wires 0.25 to 1.50 mm² / 24 to 16 AWG
With wire end sleeves 0.25 to 0.75 mm² / 24 to 20 AWG
Distance between contacts
Left - Right 4.2 mm
Above - Below 8.25 mm
Electrical properties
Nominal voltage 24 VDC
Max. voltage 50 VDC
Nominal current 2 A / contact
Contact resistance ≤5 mΩ
Ambient conditions
Temperature
Operation Corresponds to the X20 module used
Relative humidity
Operation Corresponds to the X20 module used
Material number:
X20TB1F
Description:
  • Tool-free wiring with push-in technology
  • Simple wire release using a screwdriver
  • Ability to label each terminal
  • Plain text labeling also possible
  • Test access for standard probes
  • Can be customer-coded

X20 24 VDC modules with 16 connections are wired using the X20TB1F terminal block.