Short description
I/O module 4 digital inputs, 2 digital outputs, 1 analog input, 1 analog output, special functions
General information
B&R ID code 0x24C3
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Analog inputs Yes, using LED status indicator and software
Digital outputs Yes, using LED status indicator and software (output error status)
Power consumption
Bus 0.01 W
Internal I/O 1.75 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
EAC Yes
KC Yes
Digital inputs
Quantity 4
Nominal voltage 24 VDC
Input characteristics per EN 61131-2 Type 1
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Typ. 3.3 mA
Input circuit Sink
Input filter
Hardware ≤2 µs
Software Default 1 ms, configurable between 0 and 25 ms in 0.2 ms increments
Connection type 1-wire connections
Input resistance Typ. 7.18 kΩ
Additional functions 20 kHz event counting, gate measurement
Switching threshold
Low <5 VDC
High >15 VDC
Insulation voltage between channel and bus 500 Veff
Event counters
Quantity 2
Signal form Square wave pulse
Evaluation Each negative edge, cyclic counter
Input frequency Max. 20 kHz
Counter 1 Input 1
Counter 2 Input 3
Counter frequency Max. 20 kHz
Counter size 16-bit
Gate time measurement
Quantity 1
Signal form Square wave pulse
Evaluation Positive edge - Negative edge
Counter frequency
Internal 48 MHz, 24 MHz, 12 MHz, 6 MHz, 3 MHz, 1.5 MHz, 750 kHz, 375 kHz, 187.5 kHz
Counter size 16-bit
Length of pause between pulses ≥100 µs
Pulse length ≥20 µs
Supported inputs Input 4
Analog inputs
Quantity 1
Input ±10 V or 0 to 20 mA / 4 to 20 mA, via different terminal connections
Input type Single-ended
Digital converter resolution
Voltage ±12-bit
Current 12-bit
Conversion time 400 µs, conversion runs asynchronous to the X2X Link cycle
Output format INT
Output format
Voltage INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
Current INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Input impedance in signal range
Voltage >1 MΩ
Current -
Load
Voltage -
Current <300 Ω
Input protection Protection against wiring with supply voltage
Permissible input signal
Voltage Max. ±15 V
Current Max. ±50 mA
Output of digital value during overload
Undershoot
Voltage 0x8001
Current 0x0000
Overshoot
Voltage 0x7FFF
Current 0x7FFF
Conversion procedure Successive approximation
Input filter Second-order low-pass filter / Cutoff frequency 1 kHz
Max. error
Voltage
Gain 0.08%
Offset 0.02%
Current
Gain 0 to 20 mA = 0.08% / 4 to 20 mA = 0.1%
Offset 0 to 20 mA = 0.03% / 4 to 20 mA = 0.16%
Max. gain drift
Voltage 0.01%/°C
Current 0 to 20 mA = 0.009 %/°C
4 to 20 mA = 0.0113 %/°C
Max. offset drift
Voltage 0.002%/°C
Current 0 to 20 mA = 0.004 %/°C
4 to 20 mA = 0.005 %/°C
Nonlinearity
Voltage <0.02%
Current <0.02%
Insulation voltage between channel and bus 500 Veff
Digital outputs
Quantity 2
Variant Current-sourcing FET
Nominal voltage 24 VDC
Switching voltage 24 VDC -15% / +20%
Nominal output current 0.5 A
Total nominal current 1 A
Connection type 1-wire connections
Output circuit Source
Output protection Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection
Diagnostic status Output monitoring with 10 ms delay
Leakage current when the output is switched off 5 µA
RDS(on) 105 mΩ
Peak short-circuit current <14 A
Switch-on in the event of overload shutdown or short-circuit shutdown Approx. 10 ms (depends on the module temperature)
Switching delay
0 → 1 <250 µs
1 → 0 <270 µs
Switching frequency
Resistive load Max. 100 Hz
Inductive load See section "Switching inductive loads".
Braking voltage when switching off inductive loads Typ. 50 VDC
Insulation voltage between channel and bus 500 Veff
Analog outputs
Quantity 1
Output ±10 V or 0 to 20 mA, via different terminal connections
Digital converter resolution 12-bit
Conversion time 300 µs, conversion runs asynchronous to the X2X Link cycle
Settling time on output change over entire range 1 ms
Switch on/off behavior Internal enable relay for startup and errors
Max. error
Voltage
Gain 0.04%
Offset 0.0225%
Current
Gain 0.05%
Offset 0.125%
Output protection Short-circuit proof
Output format
Voltage INT 0x8001 - 0x7FFF / 1 LSB = 0x0010 = 4.882 mV
Current INT 0x0000 - 0x7FFF / 1 LSB = 0x0010 = 9.766 µA
Load per channel
Voltage Max. ±10 mA, load ≥ 1 kΩ
Current Max. load is 400 Ω
Max. gain drift
Voltage 0.012%/°C
Current 0.014 %/°C
Max. offset drift
Voltage 0.0075% / °C
Current 0.03 %/°C
Error caused by load change
Voltage Max. 0.02%, from 10 MΩ → 1 kΩ, resistive
Current Max. 0.5%, from 1 Ω → 400 Ω, resistive
Nonlinearity <0.1%
Insulation voltage between channel and bus 500 Veff
Electrical properties
Electrical isolation
Channel isolated from bus

Channel not isolated from channel
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.
Pitch 12.5+0.2 mm
Número do material:
X20CM8281
Descrição:
  • Digital and analog channels
  • Selectable current and voltage for AI and AO
  • Counter functions

The module is a universal mixed module. On this module, digital I/O and analog I/O are combined. A current or voltage signal can be used for the analog I/O as desired. Counter functions on two of the digital inputs expand the range of use.

Acessórios obrigatórios
Bus modules
X20BM11 X20 bus module, 24 VDC keyed, internal I/O power supply connected through
X20BM15 X20 bus module, with node number switch, 24 VDC keyed, internal I/O power supply connected through
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Atualizações de HW Automation Studio Version (Data) Download
V2.6 HW Upgrade (X20CM8281) EXE / 1 MB
V3.0 HW Upgrade (X20CM8281) EXE / 2 MB
V4.0 HW Upgrade (X20CM8281) EXE / 1 MB
Certificados Version (Data) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
ABS Certificate of Product Design Assessment - X20 IO Series PDF / 2 MB
BV Type Approval Certificate - X20 PDF / 556 KB
Compass Safe Distance Certificate - X20 PDF / 1 MB
DNV Type Approval Certificate - X20 PDF / 194 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Lloyds Register PDF / 502 KB
RINA Type Approval Certificate - X20 / Power Panel T30 PDF / 1 MB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB
Documentação Version (Data) Download
Data sheet X20CM8281 PDF / 668 KB
Installation- / EMC-Guide PDF / 20 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Modelos Electro ou EPLAN) Version (Data) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. Modelos) Version (Data) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Por favor escolha o país e o idioma

B&R Logo