7EC020.60-2

General information
Module type Embedded controller
Power consumption <6 W
Certifications
CE Yes
UKCA Yes
UL cULus E115267
Industrial control equipment
Controller
Operating system AC140 (version E2.82 and later)
Processor clock 100 MHz
DRAM 32 MB
SRAM 32 kB
Inputs/Outputs
Module-side connection 8-pin multipoint connector
Configuration of digital inputs/outputs Individually configurable as inputs or outputs
Interfaces
Interface IF1
Type RS232
Variant 9-pin male DSUB connector
Status indicators 232 LED
Max. transfer rate 115.2 kbit/s to 19200 kbit/s at 15 m
Interface IF2
Type CAN electrically isolated
Variant 9-pin male DSUB connector
Status indicators CAN LED
Max. transfer rate 50 kbit/s at 1000 m to 500 kbit/s at 60 m
Network-capable Yes
Bus terminating resistor Externally wired
Interface IF4
Type X2X Link master electrically isolated
Variant 4-pin multipoint connector
Status indicators X2X LED
Max. distance 100 m
Network-capable YES, network topology: Line
Interface IF6
Type Ethernet IEEE 802.3
Variant Female RJ45 connector
Status indicators ACT LED
Max. distance 100 m
Transfer rate 10/100 Mbit/s
Incremental encoders
Counter size 16-bit
Input frequency Max. 20 kHz
Evaluation 4x
Signal form Square wave pulse
Inputs A/B on input 1/2, reference pulse on input 3
Digital inputs
Quantity Max. 3
Input voltage 24 VDC
Circuit Sink
Input delay <5 µs
Electrical isolation Input - PLC
Event counters
Signal form Square wave pulse
Input frequency Max. 100 kHz
Inputs Counter on input 1
Pulse length Min. 5 μs
Counter size 32-bit
Gate measurement
Signal form Square wave pulse
Counter frequency 31.25 kHz/4 MHz internal, max. 100 kHz external
Input frequency Max. 100 kHz
Period measurement
Signal form Square wave pulse
Input frequency Max. 100 kHz
Counter frequency 31.25 kHz/4 MHz internal, max. 100 kHz external
Digital outputs
Nominal voltage 24 VDC
Output protection Shutdown in the event of overcurrent or short circuit
Nominal current 500 mA
Switching frequency (resistive load) Max. 100 Hz
Switching delay Typ. 250 μs
Interface type Max. 3
Type High-side transistor outputs, readable
Electrical isolation
Input - PLC Yes
Operating conditions
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation 0 to 45°C
Storage -25 to 55°C
Relative humidity
Operation 5 to 95%
Mechanical properties
Note Backup battery included in delivery
Dimensions
Width 43 mm
Height 122 mm
Depth 110 mm
Número do material:
7EC020.60-2
Descrição:
  • RS232 interface (IF1) for programming and configuring using B&R Automation Studio
  • CAN interface (IF2) for connecting to a CAN network
  • X2X Link interface (IF4)
  • Ethernet interface (IF6) for connecting to an Ethernet network
  • ARNCO (only on 7EC020.61-2)

In addition, a maximum of three digital inputs / outputs are provided. The digital inputs and outputs can be configured individually as input or output. Additional functions such as a counter function with direction switching (stepper motor) or period and gate measurement are integrated.

Embedded controller, x86 100 MHz Intel compatible, 32 MB DRAM, 32 kB SRAM, removable application memory: CompactFlash, 1 CAN interface, 1 X2X Link master interface, 1 Ethernet interface 100BASE-T, 1 RS232 interface, 3 digital mixed channels optionally configurable as inputs or outputs, 24 VDC, 0.5 A, order application memory separately! Order terminal blocks 0TB708 and 0TB704 separately!
Acessórios obrigatórios
CompactFlash cards
0CFCRD.016GE.02 CompactFlash 16 GB extended temp.
0CFCRD.0512E.02 CompactFlash 512 MB extended temp.
0CFCRD.1024E.02 CompactFlash 1024 MB extended temp.
0CFCRD.2048E.02 CompactFlash 2048 MB extended temp.
0CFCRD.4096E.02 CompactFlash 4096 MB extended temp.
0CFCRD.8192E.02 CompactFlash 8 GB extended temp.
5CFCRD.2048-06 CompactFlash 2 GB B&R (SLC)
Terminal blocks
0TB708.91 Accessory terminal block, 8-pin, cage clamp terminal block 1.5 mm²
Undefined
5CFCRD.0064-02 CompactFlash 64 MB ATA/IDE SanDisk
5CFCRD.0128-02 CompactFlash 128 MB ATA/IDE SanDisk
5CFCRD.0256-02 CompactFlash 256 MB ATA/IDE SanDisk
5CFCRD.0512-02 CompactFlash 512 MB ATA/IDE SanDisk
5CFCRD.1024-02 CompactFlash 1 GB ATA/IDE SanDisk
5CFCRD.2048-02 CompactFlash 2 GB ATA/IDE SanDisk
Acessórios opcionais
Infrastructure components
0AC912.9 Bus adapter, CAN, 1 CAN interface
0AC913.92 Bus adapter, CAN, 2 CAN interfaces, including 30 cm attachment cable (DSUB)
0G1000.00-090 Bus connector, RS485, for PROFIBUS networks
7AC911.9 Bus connector, CAN
Atualizações de HW Automation Studio Version (Data) Download
V2.6 HW Upgrade (7EC020.60-2) EXE / 657 KB
V3.0 HW Upgrade (7EC020.60-2) EXE / 656 KB
Documentação Version (Data) Download
Compact I/O User's Manual PDF / 4 MB
Embededed Controller Users's Manual PDF / 2 MB
M-CAD (Mechan. Modelos) Version (Data) Download
3D File DXF/STEP Embedded Controller ZIP / 4 MB

Por favor escolha o país e o idioma

B&R Logo