3IF789.9

Short description
Communication module 1x X2X Link master, 1x Ethernet POWERLINK managing or controlled node
General information
LEDs X2X Link Rx/Tx, POWERLINK
B&R ID code 0x13E2
LEDs
Quantity 6
Status indicators Send/receive data for IF1
Status of the POWERLINK station, network activity, link/collision for IF2
Diagnostics
Bus function (IF2) Yes, using status LED and software status
Data transfer (IF1) Yes, using status LED and software status
Station status (IF2) Yes, using status LED and software status
Power consumption
3.3 VDC 2.3 W
5 VDC 0.5 W
Total 2.8 W
Electrical isolation
IF1 - IF2 Yes
PLC - IFx Yes
Certifications
CE
UKCA Yes
UL
EAC Yes
KC Yes
Interfaces
Interface IF1
Type X2X Link master
Variant 4-pin multipoint plug
Number of stations Max. 253
Internal bus power supply No
Network topology Line
Distance between 2 stations Max. 100 m
Bus terminating resistor Internal
Interface IF2
Fieldbus Ethernet POWERLINK
Type 100 Base-T (ANSI/IEEE 802.3)
Variant Shielded RJ45 port
Line length Max. 100 m between two stations (segment length)
Transfer rate 100 Mbit/s
In/Out buffer 20 kB
Operating conditions
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation 0 to 60°C
Vertical mounting orientation 0 to 60°C
Storage -25 to 70°C
Transport -25 to 70°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x TB704 terminal block separately
Slot Insert e.g. in CP360
Número do material:
3IF789.9
Descrição:
aPCI interface module, 1 POWERLINK interface, managing or controlled node, 1 X2X Link master interface, electrically isolated, order 1x terminal block TB704 separately!
Acessórios obrigatórios
Terminal blocks
0TB704.9 Accessory terminal block, 4-pin, screw clamp terminal block 2.5 mm²
0TB704.91 Accessory terminal block, 4-pin, push-in terminal block 2.5 mm²
Atualizações de HW Automation Studio Version (Data) Download
V2.6 HW Upgrade (3IF789.9) EXE / 508 KB
V3.0 HW Upgrade (3IF789.9) EXE / 508 KB
V4.0 HW Upgrade (3IF789.9) EXE / 423 KB
Documentação Version (Data) Download
Datasheet 3IF789.9 PDF / 671 KB