Short description
I/O module | 4 analog inputs ±10 V or 0 to 20 mA |
General information
Analog inputs
Electrical properties
Electrical isolation |
Channel isolated from bus Channel not isolated from channel |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
Pitch | 12.5+0.2 mm |
Référence produit:
X20AI4636Description:
- 4 analog inputs
- Current or voltage signal configuration for the entire module
- 16-bit digital converter resolution
- Minimum conversion time of 40 µs for all inputs
- The conversion time for the entire module can be configured in 0.02 µs steps.
- Maximum 14 samples (16-bit) for the entire module per X2X Link cycle
- Oversampling: Up to 16 analog values per channel (internal)
- Timestamp for the last conversion of an X2X Link cycle
The module is equipped with 4 inputs with 16-bit digital converter resolution. It is possible to select between the current and voltage signal using different terminals. With the oversampling function, up to 16 analog values per channel can be recorded.
Accessoires obligatoires
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V2.7 HW Upgrade (X20AI4636) | EXE / 1 Mo | |
V3.0 HW Upgrade (X20AI4636) | EXE / 2 Mo | |
V4.0 HW Upgrade (X20AI4636) | EXE / 911 Ko |
Documentation | Version (date) | Téléchargement |
---|---|---|
Data sheet X20AI4636 | PDF / 511 Ko | |
Installation- / EMC-Guide | PDF / 20 Mo | |
X20 System User´s Manual | PDF / 7 Mo |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 Mo |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 Ko | |
3D File STEP X20 I/O-Slice | ZIP / 872 Ko | |
Dimensions PDF X20 Electronic module | PDF / 3 Ko |