Short description
Bus controller PROFIBUS DP V0 slave
General information
B&R ID code 0x1F1C
Status indicators Module status, bus function, data transfer
Diagnostics
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator
Data transfer Yes, using LED status indicator
Power consumption
Bus 2.3 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
Interfaces
Fieldbus PROFIBUS DP V0 slave
Variant 9-pin female DSUB connector
Max. distance 1200 m
Transfer rate Max. 12 Mbit/s
Default transfer rate Automatic transfer rate detection
Min. cycle time
Fieldbus No limitation
X2X Link 400 μs
Synchronization between bus systems possible No
Electrical properties
Electrical isolation PROFIBUS isolated from I/O
PROFIBUS not isolated from bus
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 or X20PS9402 separately.
Order 1x bus base X20BB80 separately.
Pitch 37.5+0.2 mm
Référence produit:
X20BC0063
Description:
  • Fieldbus: PROFIBUS DP
  • I/O configuration via the fieldbus
  • Extensive device, module, and channel diagnosis according to PROFIBUS DP standard
  • Communication with X2X Link I/O nodes even works when some nodes are missing or without power

PROFIBUS DP is based on the physics of the RS485 interface. Data transfer is controlled using a hybrid bus access procedure: Active stations receive communication rights via a token passing procedure and can then access all stations on the network according to the master-slave principle. The maximum time of circulation for a token can be configured, which results in a defined cycle time.

Access represents various services for the user for both cyclic and for acyclic data transfer.

This bus controller makes it possible to connect X2X Link I/O nodes to PROFIBUS DP. It supports PROFIBUS DP with all of its options and other additional properties. In addition to the device, module and channel diagnostics provided in the PROFIBUS standard, it is also possible, for example, to switch to the slot diagnostics option in S7 format.

X20 or other modules based on X2X Link can be connected to the bus controller. The configuration of the modular system is optimally supported by PROFIBUS DP.

With multifunction modules, the bus controller supports only the default function model in the event of automatic configuration by the bus controller (see the respective module description).

Accessoires obligatoires
System modules for bus controllers
X20BB80 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20PS9400 X20 power supply module, for bus controller and internal I/O power supply X2X Link power supply
X20PS9402 X20 power supply module, for bus controller and internal I/O power supply, X2X Link supply, supply not galvanically isolated
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Accessoires optionnels
Infrastructure components
0G1000.00-090 Bus connector, RS485, for PROFIBUS networks
Certifications Version (date) Téléchargement
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
Profibus Certificate X20BC0063 PDF / 197 KB
Safe cutoff of potential groups PDF / 211 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB
Documentation Version (date) Téléchargement
BC Service Channel PDF / 1 MB
Data sheet X20BC0063 PDF / 159 KB
Installation- / EMC-Guide PDF / 20 MB
PROFIBUS Bus Controller User's manual PDF / 7 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (modèles Electro ou EPLAN) Version (date) Téléchargement
X20 EPLAN P8 from V2.4 EXE / 160 MB
Fichiers de description d'équipement bus de terrain Version (date) Téléchargement
BC Service Channel Example ZIP / 15 MB
X20BC0063 GSD Package ZIP / 13 MB
M-CAD (modèles mécaniques) Version (date) Téléchargement
3D File DXF/STEP X20 Bus Controller X20BC0063 ZIP / 26 KB
Dimensions PDF X20 Bus Controller X20BC0063 PDF / 4 KB

Veuillez sélectionner un pays et une langue