Short description
Communication module | 1x RS232, 1x PROFIBUS DP V0 slave |
General information
Status indicators | Transmit/Receive data per interface |
Diagnostics | |
Data transfer | Yes, using LED status indicators |
Power consumption | |
3.3 VDC | 0.15 W |
5 VDC | 1.2 W |
Total | 1.35 W |
Electrical isolation | |
IF1 - IF2 | Yes |
PLC - IF1 | No |
PLC - IF2 | Yes |
Certifications | |
CE | Yes |
UKCA | Yes |
HazLoc |
cULus HazLoc E180196 Industrial control equipment for hazardous locations Class I, Division 2, Groups ABCD |
EAC | Yes |
KC | Yes |
Interfaces
Interface IF1 | |
Signal | RS232 |
Variant | 9-pin male DSUB connector |
Max. distance | 900 m |
Transfer rate | Max. 115.2 kbit/s |
Interface IF2 | |
Fieldbus | PROFIBUS DP V0 slave |
Variant | 9-pin female DSUB connector |
Max. distance | 1200 m |
Transfer rate | Max. 12 Mbit/s |
Operating conditions
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | 0 to 60°C |
Storage | -25 to 70°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Mechanical properties
Slot | Slot, e.g. in the CP360 |
Número de material:
3IF761.9Descripción:
- Profibus DP slave connection
- RS232 can be configured as an online interface
Accesorios opcionales
Infrastructure components
0G1000.00-090 | Bus connector, RS485, for PROFIBUS networks |
Undefined
0AC916.9 | Bus termination, RS485, active for PROFIBUS networks, remote I/O standard top-hat rail mounting supply voltage: 120 / 230 VAC |
Actualizaciones de hardware de Automation Studio | Versión (fecha) | Descargar |
---|---|---|
AS 2.6 Upgrade 3IF761.9 | EXE / 429 KB | |
AS 3.0 Upgrade 3IF761.9 | EXE / 414 KB | |
V4.0 HW Upgrade (3IF761.9) | EXE / 330 KB |
Archivos de descripción de equipos de bus de campo | Versión (fecha) | Descargar |
---|---|---|
3IF761.9 GSD Package | ZIP / 7 KB |
Documentación | Versión (fecha) | Descargar |
---|---|---|
Datasheet 3IF761.9 | PDF / 467 KB |