General information
Terminals | Stable screw clamp terminal blocks |
Status indicators | |
Operation | LED, green |
Overload | LED, red |
Certifications |
Terminal block
Connection cross section | |
Output | |
Inflexible | 0.5 to 16 mm² / 22 to 8 AWG |
Flexible | 0.50 to 10 mm² / 22 to 8 AWG |
Input | |
Inflexible | 0.5 to 6 mm² / 20 to 10 AWG |
Flexible | 0.5 to 4 mm² / 20 to 10 AWG |
Input
Input voltage | 3 AC 340-575 V, 47-63 Hz |
Input current | 3x 3.0 A |
External fuse protection | Via three commercially available thermomagnetic circuit breakers |
Transient immunity | Active transient filter, thus transient-proof per VDE 0160 / W2 |
Output (including logic)
Output noise suppression | Device complies with EN 61000-6-3 (class B) |
Output power | 960 W |
Nominal voltage | DC 24-28 V (default setting: 24.5 V ±0.5%) |
Power back immunity | 35 V |
Protection functions | Output is short-circuit, overload- and no-load proof. |
Overvoltage protection | 32 V ±10%: Transition to hiccup operation |
Permissible output load | |
TU = 0 to 45°C | 24 V / 45 A (1080 W) or 28 V / 38 A (1064 W) |
TU = 0 to 60°C | 24 V / 40 A (960 W) or 28 V / 35 A (980 W) |
Efficiency, reliability
Efficiency | Typ. 92.5% (400 VAC, 24 V / 40 A) |
MTBF | 305,000 h |
Losses | Typ. 78 W (400 VAC, 24 V / 40 A) |
Ambient conditions
Temperature | |
Operation | 0 to 70°C |
Storage | -25 to 85°C |
Relative humidity | |
Operation | Max. 95% |
Mechanical properties
Installation | Easy snap-on mounting onto the top-hat rail |
Dimensions | |
Width | 275 mm |
Height | 124 mm |
Depth | 117 mm (plus top-hat rail) |
Weight | 3300 g |
Ventilation/Cooling | Normal convection, no fan required |
Número de material:
0PS340.1Descripción:
24 VDC power supply unit, 3-phase, 40 A, input 400..500 VAC (3 phases), wide range, top-hat rail installation
Documentación | Versión (fecha) | Descargar |
---|---|---|
Datasheet 0PS340.1 | PDF / 826 KB |