Please choose country and language

Short description
Interfaces POWERLINK
System module CPU
General information
Cooling Fanless
B&R ID code 0xE649
System requirements
Automation Studio 4.1.6 or later
Automation Runtime F4.09 or later, F4.10 or later, A4.23 or later
SafeDESIGNER 4.1.0 or later
Safety Release 1.7 or later
Status indicators CPU function, POWERLINK, SafeKEY
Diagnostics
CPU function Yes, using status LED
POWERLINK Yes, using status LED
SafeKEY Yes, using status LED
Power consumption 5.3 W
Blackout mode
Scope Network segment
Function Programmable
Standalone mode Yes
Power consumption for X2X Link power supply 1.42 W
Power consumption
Internal I/O 0.6 W
Electrical isolation
Fieldbus - X2X Link Yes
Fieldbus - I/O Yes
Certifications
CE Yes
Functional safety cULus FSPC E361559
Energy and industrial systems
Certified for functional safety
ANSI UL 1998:2013
Functional safety IEC 61508:2010, SIL 3
EN 62061:2013, SIL 3
EN ISO 13849-1:2015, Cat. 4 / PL e
IEC 61511:2004, SIL 3
Functional safety EN 50156-1:2004
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV GL Temperature: A (0 - 45°C)
Humidity: B (up to 100%)
Vibration: A (0.7 g)
EMC: B (bridge and open deck)
KR Yes
EAC Yes
Safety characteristics
EN ISO 13849-1:2015
Category Cat. 4
PL PL e
DC >94%
MTTFD 2500 years
Mission time Max. 20 years
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
SIL CL SIL 3
SFF >90%
PFH / PFHd
Module <1*10-10
openSAFETY wired Negligible
openSAFETY wireless <1*10-14 * Number of openSAFETY packets per hour
PFD <2*10-5
Proof test interval (PT) 20 years
Functionality
Communication with each other Yes
Support for Safe Commissioning Options
BOOL 512
INT 64
UINT 64
DINT 64
UDINT 64
SafeMOTION support Yes, depends on the number of available operating licenses on the SafeKEY
Timing precision Time * 0.05 + Cycle time of the safety application
Shortest task class cycle time 1 ms
Max. number of openSAFETY nodes 280, depends on the number of available operating licenses on the SafeKEY and available resources
Max. number of POWERLINK controlled nodes 100
Data exchange between CPU and SL
Max. total data width for each direction 512 bytes
Max. number of data points for each direction
BOOL 1024
INT 128
UINT 128
DINT 64
UDINT 64
Limit values for SafeDESIGNER application
Max. resources available for SafeDESIGNER info window entries
FB instances 4096
Marker memory 131,072 bytes
Stack memory 32,768 bytes
Memory for safe input data 2048 bytes
Memory for safe output data 2048 bytes
Memory for standard input data 1024 bytes
Memory for standard output data 1024 bytes
Marker count 8192
Additional SafeDESIGNER limit values
Max. number of function block types 512
Max. number of force variables 64
Max. number of variable with variable status 1023
Input SL / BC / X2X Link power supply
Input voltage 24 VDC -15% / +20%
Input current Max. 0.9 A
Fuse Integrated, cannot be replaced
Reverse polarity protection Yes
Output SL / BC / X2X Link power supply
Nominal output power 7 W
Parallel connection Yes
Redundant operation Yes
Overload characteristics Short-circuit proof, temporary overload
Input I/O power supply
Input voltage 24 VDC -15% / +20%
Fuse Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection Yes
Output I/O power supply
Nominal output voltage 24 VDC
Behavior on short circuit Required line fuse
Permissible contact load 10 A
Interfaces
Fieldbus POWERLINK controlled node
Type Type 3
Variant 2x shielded RJ45 port (hub)
Line length Max. 100 m between 2 nodes (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex No
Autonegotiation Yes
Auto-MDI/MDIX Yes
Min. cycle time
Fieldbus 200 µs
X2X Link 200 µs
Synchronization between bus systems possible Yes
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level 0 to 2000 m, no limitation
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation 0 to 60°C
Vertical mounting orientation 0 to 45°C
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order SafeKEY and SafeLOGIC range of functions using the X20MK configurator.
X20 end cover plate (right) included in delivery.
12-pin X20 terminal block, safety-keyed, included in delivery.
SafeKEY cover included in delivery.
Dimensions
Width 62.5+0.2 mm
Height 99 mm
Depth 75 mm
Weight 190 g
Material number:
X20SL8101
Description:
  • openSAFETY manager for up to 280 SafeNODEs
  • Flexibly programmable using Automation Studio / SafeDESIGNER
  • Innovative management of safe machine options (SafeOPTION)
  • Parameter and configuration management

The module is equipped with SafeLOGIC functionality that allows it to safely execute applications designed in SafeDESIGNER. The module can be used in safety-related applications up to PL e or SIL 3.

In addition, the module coordinates the safety-related communication of all modules involved in the application. In this context, the module also monitors the configuration of these modules and carries out autonomous parameter downloads to the modules whenever necessary. This guarantees a consistent and correct module configuration in the network from a safety standpoint in all scenarios involving module replacement and service. These services are performed by the SafeLOGIC controller.

Mandatory Accessories
Accessories
X20MK0223 X20 SafeKEY, 8 MB, for the X20SL81xx series, exclusively for mapp Safety, range of license functions determined via Technology Guarding in Automation Runtime
X20MKXXXX.XXX.XXX "Safety Technology Guarding" defines the range of functions available for applications using X20SL81xx- or X20cSL81xx-series SafeLOGIC controllers. Licenses are stored on a SafeKEY dongle. The functions required for the application must be put together in the X20MK configurator by selecting a SafeKEY with a sufficient amount of memory, a coated/non-coated variant and the necessary technology functions. Each solution is delivered exclusively as a set consisting of the SafeKEY and the activated licenses for the selected technology functions.
Automation Studio HW Upgrades Version (Date) Download
V4.0 HW Upgrade (X20SL8101) EXE / 6 MB
V4.6 HW Upgrade (X20SL8101) EXE / 2 MB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
DNV GL Type Approval Certificate - X20 / Power Panel T30 PDF / 171 KB
E115267 UL CoC X20 PDF / 1 MB
FS Certificate mapp Safety PDF / 5 MB
FS Zertifikat SafeDESIGNER, SafeLOGIC, SafeIO PDF / 420 KB
FTZU 09 ATEX 0083X PDF / 697 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Documentation Version (Date) Download
Data sheet X20(c)SL81xx - Legacy PDF / 7 MB
Data sheet X20(c)SL81xx - mapp Safety PDF / 4 MB
information sheet SafeLOGIC PDF / 553 KB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X20SL810x ZIP / 7 MB
Tools / Utilities / Examples Version (Date) Download