Input
|
Resistance measurement with constant current supply for 2- or 3-wire connections
|
|
Digital converter resolution
|
16- or 18-bit
|
|
Conversion time
|
Configurable for each channel
|
|
Conversion procedure
|
Sigma-delta
|
|
Output format
|
INT/DINT for temperature measurement UINT for resistance measurement
|
|
Sensor
|
|
|
Sensor type
|
Configurable per channel
|
|
PT100
|
-200 to 850°C
|
|
PT1000
|
-200 to 850°C
|
|
Resistance measurement range
|
0.01 to 600 Ω / 0.1 to 4800 Ω
|
|
Resistance measurement resolution
|
600 Ω: 0.01 Ω / 4800 Ω: 0.1 Ω
|
|
Sensor standard
|
EN 60751
|
|
Isolation voltage between channel and bus
|
1210 VDC
|
|
Linearization method
|
Internal
|
|
Measuring current
|
250 µA with Pt100 or 600 Ω 100 µA with Pt1000 or 4800 Ω
|
|
Reference
|
5000 Ω ±0.1%
|
|
Permitted input signal
|
Max. ±32 V
|
|
Max. error at 25°C
|
|
|
Gain
|
Pt100 and 600 Ω: ±0.15% / Pt1000 and 4800 Ω: ±0.15%
|
|
Offset
|
Pt100 and 600 Ω: ±0.04% / Pt1000 and 4800 Ω: ±0.015%
|
|
Max. gain drift
|
Pt100 and 600 Ω: ±0.015 %/°C Pt1000 and 4800 Ω: ±0.015 %/°C
|
|
Max. offset drift
|
Pt100 and 600 Ω: ±0.005 %/°C Pt1000 and 4800 Ω: ±0.0015 %/°C
|
|
Non-linearity
|
<0.005%
|
|
Standardized value range for resistance measurement
|
600 Ω: 0.01 to 600.00 Ω / 4800 Ω: 0.1 to 4800.0 Ω
|
|
Crosstalk between channels
|
<-88 dB
|
|
Temperature sensor resolution
|
|
|
PT100
|
1 LSB = 0.1 or 0.01°C
|
|
PT1000
|
1 LSB = 0.1 or 0.01°C
|
|
Common-mode rejection
|
|
|
50 Hz
|
>96 dB
|
|
DC
|
>96 dB
|
|
Temperature sensor standardization
|
|
|
PT100
|
INT: -200.0 to 850.0°C DINT: -200.00 to 850.00°C
|
|
PT1000
|
INT: -200.0 to 850.0°C DINT: -200.00 to 850.00°C
|
|
Temperature measurement monitoring
|
|
|
Range exceeded (neg.)
|
0x8001
|
|
Above upper range limit
|
0x7FFF
|
|
Open line
|
0x7FFF
|
|
General error
|
0x8000
|
|
Open inputs
|
0x7FFF
|
|
Resistance measurement monitoring
|
|
|
Above upper range limit
|
0xFFFF
|
|
Open line
|
0xFFFF
|
|
General error
|
0xFFFF
|
|
Open inputs
|
0xFFFF
|