Short description
Bus controller CANopen slave
General information
B&R ID code 0x2A00
Status indicators Module status, bus function, data transfer, terminating resistor
Diagnostics
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator and software
Data transfer Yes, using LED status indicator
Terminating resistor Yes, using LED status indicator
Power consumption
Bus 1.5 W (rev. <H0: 2 W)
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
DNV Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
ABS Yes
Interfaces
Fieldbus CANopen slave
Variant 5-pin male multipoint connector
Max. distance 1000 m
Transfer rate Max. 1 Mbit/s
Default transfer rate Automatic transfer rate detection or fixed setting
Min. cycle time
Fieldbus No limitation
X2X Link 500 μs
Synchronization between bus systems possible No
Terminating resistor Integrated in module
Electrical properties
Electrical isolation CANopen isolated from I/O
CANopen not isolated from bus
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Up to 100%, condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block TB2105 separately.
Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20cPS9400 separately.
Order 1x bus base X20cBB80 separately.
Pitch 37.5+0.2 mm
Артикул:
X20cBC0043-10
Описание:
  • Fieldbus: CANopen
  • Auto-configuration of I/O modules
  • I/O configuration via the fieldbus
  • Constant response times even with large amounts of data (max. 32 Rx and 32 Tx PDOs)
  • Configurable I/O cycle (0.5 to 4 ms)
  • Configurable transfer rate or automatic transfer rate detection
  • Heartbeat consumer and producer
  • Emergency producer
  • 2x SDO server, NMT slave
  • Simple bootup (autostart)
  • Terminal access via serial interface on the X20PS9400
  • Integrated terminating resistor
X20 bus controller, coated, 1 CANopen interface, order 1x terminal block TB2105 separately! Order bus base, power supply module and terminal block separately!
Необходимые аксессуары
System modules for bus controllers
X20cBB80 Базовый модуль X20, с покрытием, для основного модуля X20 (BC, HB и т. д.) и модуля питания X20, заглушки X20 (левая и правая) X20AC0SL1/X20AC0SR1 включены в поставку
X20cPS9400 Модуль питания X20, с покрытием, для контроллера шины и внутренней шины ввода/вывода, питание шины X2X
Terminal blocks
0TB2105.9010 Принадлежность клеммная колодка, 5-контактная, винтовые зажимы 2,5 мм²
0TB2105.9110 Принадлежность клеммная колодка, 5-контактная, пружинные зажимы 2,5 мм²
X20TB12 Клеммная колодка X20, 12 контактов, кодировка 24 В постоянного тока
E-CAD (шаблоны Electro или EPLAN) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 158 МБ
Документация Version (Date) Download
Datasheet X20(c)BC0043-10 PDF / 1,005 кБ
Installation- / EMC-Guide PDF / 20 МБ
X20 System User´s Manual PDF / 7 МБ
Обновление Automation Studio HW Version (Date) Download
V4.3 HW Upgrade (X20cBC0043-10) EXE / 730 кБ
Файл описания полевых устройств Version (Date) Download
CANopen-10_PDO_Mapping_Tool ZIP / 373 кБ
X20cBC0043-10 EDS Package ZIP / 34 кБ

Выберите регион и язык:

B&R Logo