General information
Status display Green LED (DC OK), threshold value Uout = 21.5 V
Insulation voltages
Input - Output 4 kV AC (type test)
2 kV AC (routine test)
Input - Ground 2 kV AC (type test)
2 kV AC (routine test)
Output - Ground 500 VDC (type test)
Connection type Screw terminal
Connection cross section
Input
Wire end sleeves Flexible cables require wire end sleeves in order to fulfill EN 62368 / UL 60950
Flexible 0.2 to 2.5 mm² / 24 to 14 AWG
Inflexible 0.2 to 2.5 mm² / 24 to 14 AWG
Output
Wire end sleeves Flexible cables require wire end sleeves in order to fulfill EN 62368 / UL 60950
Flexible 0.5 to 4 mm² / 20 to 10 AWG
Inflexible 0.5 to 6 mm² / 20 to 10 AWG
Wire stripping length 9 mm (input)
14 mm (output)
Certifications
CE Yes
UKCA Yes
UL cULus E123528
Industrial control equipment
Input
Nominal input voltage 100 to 240 VAC
Input voltage AC 85 to 264 V (wide range), 45 to 65 Hz
Input current Approx. 4.6 A (120 VAC)
Approx. 2.4 A (230 VAC)
Inrush current limiting <15 A
I2t 1.4 A2s
Power failure bypass >13 ms (120 VAC)
>13 ms (230 VAC)
Switch-on time <1 s (typical)
Power factor (cos φ) 0.99
Leakage current to PE <3.5 mA
Protective circuit Transient surge protection with varistor
Internal fuse 10 A slow-blow
Required line fuse for line protection 16 A (characteristic B)
Input voltage <90 VAC Derating from output current: 2.5% per °C
Output
Nominal voltage 24 VDC ±1%
Output power 480 W
Setting range for output voltage 22.5 to 29.5 VDC
Output current
-25 to 55°C 20.0 A
>55°C Derating: 2.5% per °C
Current limiting Approx. 25 A (for short circuit)
Control deviation <1% (static load change 10 to 90%)
<2% (dynamic load change 10 to 90%)
<0.1% (input voltage change ±10%)
Rise time <2 ms (UOUT (10 to 90%))
Residual ripple <10 mVSS
Switching peaks <80 mVSS
Can be connected in parallel Yes, to establish redundancy and increase capacity
Can be connected in series Yes
Max. capacitive load Unlimited
Protection against internal overvoltages Yes, limited to <35 VDC
Protection functions Output protected against continuous short circuit, open circuit and overload
Power back immunity Max. 35 VDC
Output noise suppression Device complies with EN 55011 (class B)
Efficiency, reliability
Efficiency >91%
MTBF >500,000 h, per IEC 61709 (SN 29500)
Power dissipation
Rated load Max. 46 W
No-load operation Max. 4 W
Operating conditions
Mounting orientation
Horizontal Yes
Vertical No
Installation elevation above sea level
Maximum 4000 m
Ventilation/Cooling Normal convection, no fan required
Degree of protection per EN 60529 IP20
Protection class I, with PE connection
Ambient conditions
Temperature
Operation -25 to 70°C (>55°C derating)
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Max. 95%, non-condensing
Vibration
Operation <15 Hz, amplitude ±2.5 mm, per IEC 60068-2-6
15 to 150 Hz, 2.3 g, 90 min
Shock
Operation 30 g in each direction, per IEC 60068-2-27
Pollution degree 2, per EN 50178
Climate category 3K3, per EN 60721
Mechanical properties
Housing
Material Steel sheet, galvanized
Side panels: Aluminum
Installation Easy top-hat rail installation (NS 35 rails, EN 60715)
Dimensions
Width 115 mm
Height 130 mm
Depth 152.5 mm
Weight 2000 g
Номер модель:
0PS1200.1
Описание:
  • 100 to 240 VAC wide-range input
  • High dielectric strength
  • Can be connected in parallel for increased capacity and redundancy
  • Reliable operation due to long power failure bypass function under full load and high MTBF (>500,000 h)
  • International certification package
  • Wide temperature range from -25 to 70°C
  • Closed metal housing
24 VDC power supply, 1-phase, 20 A, input 100 to 240 VAC, wide range, top-hat rail installation
M-CAD (Механические Шаблоны Версия (Дата) Загрузка
3D file DXF/STEP 0PS1200.1 ZIP / 594 кБ
Документация Версия (Дата) Загрузка
Datasheet 0PS1200.1 PDF / 475 кБ
Installation- / EMC-Guide PDF / 20 МБ
Общие сведения Версия (Дата) Загрузка
Power Supply Statement-Directive 2009/125/EC PDF / 20 кБ
Сертификаты Версия (Дата) Загрузка
EU Declaration Power supplies PDF / 129 кБ

Укажите страну и язык

B&R Logo