| I/O module | 2 full-bridge strain gauge inputs |
General information
Full-bridge strain gauge
| Strain gauge factor | 2 to 256 mV/V, configurable using software |
| Connection | 4-wire connections |
| Input type | Differential, used to evaluate a full-bridge strain gauge |
| Digital converter resolution | 24-bit |
| Conversion time | 200 µs |
| Data output rate | 5000 samples per second and per channel (fDATA) |
| Input filter | |
| Cutoff frequency | 2.5 kHz |
| Orderliness | 3 |
| Slope | 60 dB |
| ADC filter characteristics | Sigma-delta, see section "Filter" |
| Operating range / Measurement sensor | 85 to 5000 Ω |
| Influence of cable length | Twisted and shielded conductors, cable length as short as possible, cable routing separate from load circuits, without intermediate terminal to sensor |
| Input protection | RC protection |
| Common-mode range |
0.6 to 3.8 VDC Permissible input voltage range (with regard to the electric potential strain gauge GND) on inputs "Input +" and "Input -" |
| Isolation voltage between input and bus | 500 Veff |
| Conversion procedure | Sigma-delta |
| Output of the digital value | |
| Broken bridge supply line | Value approaching 0 |
| Broken sensor line | Value approaching ±end value (status bit "Open circuit" set in register "Module status") |
| Valid value range | 0xFF800001 to 0x007FFFFF (-8,388,607 to 8,388,607) |
| Strain gauge supply | |
| Voltage | 5.5 VDC / Max. 65 mA per channel |
| Short circuit protection, overload protection | Yes |
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation at altitudes above sea level | |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Protection in accordance with EN 60529 | IP20 |
Environmental conditions
| Temperature | |
| Operation | |
| Horizontal installation | -25 to 60°C |
| Vertical installation | -25 to 50°C |
| Derating | See section "Hardware configuration" |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Mechanical characteristics
| Note |
Order 1x terminal block X20TB1F separately. Order 1x bus module X20BM11 separately. |
| Spacing | 12.5+0.2 mm |
Número do material:
X20AIA744Descrição:
- 2 full-bridge strain gauge inputs
- 5 kHz data output rate for both channels
- Independently configurable strain gauge factor and filter level for each of the 2 channels
This module works with 4-wire strain gauge load cells. The concept applied by the module requires compensation in the measurement system. This compensation eliminates the absolute uncertainty in the measurement circuit, such as component tolerances, effective bridge voltage or zero offset. The measurement precision refers to the absolute (compensated) value, which will only change as a result of changes in the operating temperature.
Acessórios obrigatórios
| Atualizações de HW Automation Studio | Version (Data) | Download |
|---|---|---|
| V3.0 HW Upgrade (X20AIA744) | EXE / 4 MB | |
| V4.0 HW Upgrade (X20AIA744) | EXE / 2 MB |
| Documentação | Version (Data) | Download |
|---|---|---|
| Datasheet X20AIA744 | PDF / 4 MB | |
| X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
| X20 System User´s Manual | PDF / 49 MB |
| E-CAD (Modelos Electro ou EPLAN) | Version (Data) | Download |
|---|---|---|
| X20 EPLAN P8 from V2.4 | EXE / 160 MB |
| M-CAD (Mechan. Modelos) | Version (Data) | Download |
|---|---|---|
| 3D File DXF/STEP X20 Electronic module | ZIP / 10 KB | |
| 3D File STEP X20 I/O-Slice | ZIP / 872 KB | |
| Dimensions PDF X20 Electronic module | PDF / 3 KB |