DWL@DWL10000808528
| Version | Langue | Système d'exploitation | Date | Taille | Type | Téléchargement |
|---|---|---|---|---|---|---|
| 1.5.0.0 | * | 30/07/2025 | 944 Ko | EXE | AS6_HW_X20BR9300.exe | |
| Description |
V6.0 HW Upgrade (X20BR9300) Revision information X20BR9300 Version 1.5.0.0: ID: TDYD-8920 The current limit values have been standardized on the HW variants. The warning LED is activated from 1.5 A. From 2.3 A, the error bit and the error LED are set. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_21.fw(241), 1\7105_22.fw(241), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.4.0.0: ID: TDYD-7659 Incorrectly configured modules were not identified on the X2X bus in certain circumstances. A dynamic hardware configuration is used for various customer applications.In this case, a default configuration is simply created in AS and the actual configuration is read out after the system has started up. Due to a hardware change of several I/O modules, only acyclic size of 12 bytes (previously 31 bytes) is accepted in the bootloader. If a module with more cyclic data (e.g. a safety module) is now configured, this module can no longer be identified on the bus. As a workaround, these "large" modules can be configured on other X2X slots. This problem can only be corrected with a new bootloader, which can onlybe delivered via production. Production will be switched to the new software accordingly. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_21.fw(210), 1\7105_22.fw(240), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.3.0.0: ID: 740420 Support new HW variant 21 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 743310 Module documentation revised Data sheet V 3.16 Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530),1\7105_21.fw(210), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.2.0.0: ID: Adaptations for Automation Studio 4.11 Channel description changed: no Configuration description changed: yes Firmware changed: no Version 1.1.0.0: ID: Adaptations for Automation Studio 4.8 Channel description changed: no Configuration description changed: yes Firmware changed: no Version 1.0.4.0: ID:636875 Module documentation revised Data sheet V3.15 Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.3.0: ID: 482825 Module documentation revised Data sheet V3.11 Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.6: ID: 402055 Documentation refreshed Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.4: ID: 391550 Handling for system designer improved X2X connection is shown to the left. Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.3: ID:375925 Extension of classification in Automation Studio 4 Adaption of filter conditions for hardware catalog. Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.2: ID: 342835 Correction of classificationin Automation Studio 4 Adaption of filter conditions for hardware catalog. Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.1: ID: 261385 Spacer in I/O map display corrected Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.0: ID: 260505 Error correction in Channel description Adverse Settings in the AS I/O configuration may cause an error on X2X Channel description changed: Yes Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.1.0: ID: 228115 Extension in IO-Mapping for SG3 CanIO Datapoints forBus current and Bus voltage added Channel description changed: Yes Configuration description changed: No Firmware changed: No Firmware:1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.0.1: ID: 182915 Correction of description text in HWC Correction of description text in HWC Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) |
|||||
| Version | Langue | Système d'exploitation | Date | Taille | Type | Téléchargement |
| 1.4.0.0 | * | 20/01/2025 | 954 Ko | EXE | AS6_HW_X20BR9300.exe | |
| Description |
V6.0 HW Upgrade (X20BR9300) Revision information X20BR9300 Version 1.4.0.0: ID: TDYD-7659 Incorrectly configured modules were not identified on the X2X bus in certain circumstances. A dynamic hardwareconfiguration is used for various customer applications. In this case, a default configuration is simply created in AS and the actual configuration is readout after the system has started up. Due to a hardware change of several I/O modules, only a cyclic size of 12 bytes (previously 31 bytes) is accepted in the bootloader. If a module with more cyclic data (e.g. a safety module) is nowconfigured, this module can no longer be identified on the bus. As a workaround, these "large" modules can be configured on other X2X slots. This problem can only be corrected with a new bootloader, which can only be delivered via production. Production will be switched to the new software accordingly. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_21.fw(210), 1\7105_22.fw(240), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.3.0.0: ID: 740420 Support new HW variant 21 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 743310 Module documentation revised Data sheet V 3.16 Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_21.fw(210), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.2.0.0: ID: Adaptations for Automation Studio 4.11 Channel description changed: no Configuration description changed: yes Firmware changed: no Version 1.1.0.0: ID: Adaptations for Automation Studio 4.8 Channel description changed: no Configuration description changed: yes Firmware changed: no Version 1.0.4.0: ID: 636875 Module documentation revised Data sheet V3.15 Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.3.0: ID: 482825 Module documentation revised Data sheet V3.11 Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.6: ID: 402055 Documentation refreshed Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.4: ID: 391550 Handling for system designer improved X2X connection is shown to the left. Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.3: ID: 375925 Extension of classification in Automation Studio 4 Adaption of filter conditions for hardware catalog. Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.2: ID: 342835 Correction ofclassification in Automation Studio 4 Adaption of filter conditions for hardware catalog. Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530),1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.1: ID: 261385 Spacer in I/O map display corrected Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.2.0: ID: 260505 Error correction in Channel description Adverse Settings in the AS I/O configuration may cause an error on X2X Channel description changed: Yes Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.1.0: ID: 228115 Extension in IO-Mapping for SG3 CanIO Datapoints for Bus current and Bus voltage added Channel description changed: Yes Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) Version 1.0.0.1: ID: 182915 Correction of description text in HWC Correction of description text in HWC Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\7105_1.fw(530), 1\7105_2.fw(530), 1\7105_5.fw(768), 1\7105_6.fw(784) |
|||||