Short description
Bus transmitter | X2X Link bus transmitter with supply for I/O and integrated X67 system power supply |
General information
X67 X2X Link power supply input
Input voltage | 24 VDC -15% / +20% |
Input current | Max. 0.5 A |
Fuse | Integrated, cannot be replaced |
Reverse polarity protection | Yes |
X67 X2X Link power supply output
Input I/O power supply
Input voltage | 24 VDC -15% / +20% |
Fuse | Required line fuse: Max. 10 A, slow-blow |
Reverse polarity protection | No |
Output I/O power supply
Nominal output voltage | 24 VDC |
Behavior on short circuit | Required line fuse |
Permissible contact load | 10 A |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 or 1x bus module X20BM15 separately. |
Pitch | 12.5+0.2 mm |
Material number:
X20BT9400Description:
- X2X Link bus transmitter
- For seamless expansion of the system
- Up to 100 m segment length
- Supply for internal I/O power supply
- Integrated X2X Link power supply of the X67 system
- Operation only on the rightmost slot
To connect an X20 system to an X67 system, a bus transmitter is simply connected to the end of the X20 block so that the X2X Link cable can be clamped. The bus transmitter also provides the X2X Link supply voltage of the X67 system. The X67 system power supply module that was previously always necessary can be omitted.
The bus transmitter module is only permitted to be operated with a bus module where the internal I/O power supply is connected through (e.g. X20BM11).
If the supply is used for the internal I/O power supply, this potential group is not permitted to be supplied by any other module. An I/O module with bus module X20BM01 must be used to isolate the potential group.
Mandatory Accessories
Bus modules
Terminal blocks
X20TB12 | X20 terminal block, 12-pin, 24 VDC keyed |
Optional Accessories
X2X Link cable
X67CA0X99.1000 | Cable for custom assembly, 100 m |
X67CA0X99.5000 | Cable for custom assembly, 500 m |
Automation Studio HW Upgrades | Version (Date) | Download |
---|---|---|
AS 3.0 Upgrade X20BT9400 | EXE / 89 KB | |
V2.7 HW Upgrade (X20BT9400) | EXE / 986 KB | |
V2.7 HW Upgrade (X20BT9400) | EXE / 986 KB | |
V3.0 HW Upgrade (X20BT9400) | EXE / 1 MB | |
V4.0 HW Upgrade (X20BT9400) | EXE / 711 KB |
Documentation | Version (Date) | Download |
---|---|---|
Data sheet X20BT9400 | PDF / 327 KB | |
Installation- / EMC-Guide | PDF / 20 MB | |
X20 System User´s Manual | PDF / 7 MB |
E-CAD (Electro or EPLAN Templates) | Version (Date) | Download |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD (Mechan. Templates) | Version (Date) | Download |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 KB | |
3D File STEP X20 I/O-Slice | ZIP / 872 KB | |
Dimensions PDF X20 Electronic module | PDF / 3 KB |