With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.
(Alternatively, a bootable CompactFlash card or a bootable USB stick can be used. Detailed information can be found in the PP300/400 User Manual)

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:


1. Update MTCX Firmware (PX32/FPGA)
The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards and must be sent to B&R for repair. Retry the aborted update process WITHOUT rebooting the Power Panel, for example by directly calling batch file UPDMTCX.BAT.

2. Exit
Ausstieg in die Shell (MS-DOS).


4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.17 / 2016-08-18 / MIK
----------------------------------------------------------------

Contents:
0019#0.fp 01.10 NEW
0019#0.fw 01.18
MTCXSVC.EXE 05.23
PPHOTFIX.EXE 01.01
LIESMICH.TXT 01.17 NEW
README.TXT 01.17 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- FPGA (0019#0.fp): Bugfix for 10.4in and 6.5in displays with LED backlight. At display power on, sporadic display flicker may occur.

ATTENTION!
Possible upgrade problems and version dependency, see above.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.16 * DOS 03/27/2014 163 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0116.zip
Açıklama Firmware Upgrade (MTCX)

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.
(Alternatively, a bootable CompactFlash card or a bootable USB stick can be used. Detailed information can be found in the PP300/400 User Manual)

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:


1. Update MTCX Firmware (PX32/FPGA)
The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards and must be sent to B&R for repair. Retry the aborted update process WITHOUT rebooting the Power Panel, for example by directly calling batch file UPDMTCX.BAT.

2. Exit
Ausstieg in die Shell (MS-DOS).


4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.16 / 2014-03-25
----------------------------------------------------------------

Contents:
0019#0.fp 01.09 NEW
0019#0.fw 01.18
MTCXSVC.EXE 05.23
PPHOTFIX.EXE 01.01
LIESMICH.TXT 01.16 NEW
README.TXT 01.16 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- FPGA (0019#0.fp): Support for Displays with LED Backlight.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.15 * DOS 01/22/2013 163 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0115.zip
Açıklama Firmware Upgrade (MTCX)

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.
(Alternatively, a bootable CompactFlash card or a bootable USB stick can be used. Detailed information can be found in the PP300/400 User Manual)

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:


1. Update MTCX Firmware (PX32/FPGA)
The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards and must be sent to B&R for repair. Retry the aborted update process WITHOUT rebooting the Power Panel, for example by directly calling batch file UPDMTCX.BAT.

2. Exit
Ausstieg in die Shell (MS-DOS).


4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.15 / 2012-12-07
----------------------------------------------------------------

Contents:
0019#0.fp 01.08
0019#0.fw 01.18 NEW
MTCXSVC.EXE 05.23
PPHOTFIX.EXE 01.01
LIESMICH.TXT 01.15 NEW
README.TXT 01.15 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- PX32 (0019#0.fw): Bugfix statistical record.
On I/O address 04111h every hour a 001h is issued (commando
ended without error). Bug exists since version V01.13.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.14 * DOS 11/29/2012 163 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0114.zip
Açıklama Firmware Upgrade (MTCX)

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.
(Alternatively, a bootable CompactFlash card or a bootable USB stick can be used. Detailed information can be found in the PP300/400 User Manual)

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:


1. Update MTCX Firmware (PX32/FPGA)
The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards and must be sent to B&R for repair. Retry the aborted update process WITHOUT rebooting the Power Panel, for example by directly calling batch file UPDMTCX.BAT.

2. Exit
Ausstieg in die Shell (MS-DOS).


4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.14 / 2012-11-22
----------------------------------------------------------------

Contents:
0019#0.fp 01.08 NEW
0019#0.fw 01.17
MTCXSVC.EXE 05.23
PPHOTFIX.EXE 01.01
LIESMICH.TXT 01.14 NEW
README.TXT 01.14 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- FPGA (0019#0.fp): Optimization of the backlight control for 10,4 in TFT color VGA displays.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.13 * DOS 02/01/2011 163 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0113.zip
Açıklama Firmware Upgrade (MTCX)

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.
(Alternatively, a bootable CompactFlash card or a bootable USB stick can be used. Detailed information can be found in the PP300/400 User Manual)

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:


1. Update MTCX Firmware (PX32/FPGA)
The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards and must be sent to B&R for repair. Retry the aborted update process WITHOUT rebooting the Power Panel, for example by directly calling batch file UPDMTCX.BAT.

2. Exit
Ausstieg in die Shell (MS-DOS).


4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.13 / 2011-01-28
----------------------------------------------------------------

Contents:
0019#0.fp 01.07
0019#0.fw 01.17
MTCXSVC.EXE 05.23
PPHOTFIX.EXE 01.01 NEW
LIESMICH.TXT 01.13 NEW
README.TXT 01.13 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- PPHOTFIX.EXE: Power Panel hotfix tool.
Sporadically it can happen at low temperature (<= 10°C) with a
5,7in QVGA TFT color display, that the backlight fails.
A problem localization to special lot numbers of this display
type is not possible, actually two reported failure.
The PPHOTFIX tool detects the display type and modifys the
corresponding value in the factoty settings if it is necessary
and also increases the file version of the factory settings
(FSET).
Affected PP300/400 hardware:
- 4PP320.0571-35
- 4PP420.0571-75
- 4PP420.0571-B5
- 4PP351.0571-35
- 4PP352.0571-35
- 4PP451.0571-75
- 4PP451.0571-B5
- 4PP452.0571-75
- 4PP452.0571-B5
- 5PP320.0571-39
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.12 * DOS 07/02/2010 162 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0112.zip
Açıklama Firmware Upgrade (MTCX)

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.
(Alternatively, a bootable CompactFlash card or a bootable USB stick can be used. Detailed information can be found in the PP300/400 User Manual)

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:


1. Update MTCX Firmware (PX32/FPGA)
The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards and must be sent to B&R for repair. Retry the aborted update process WITHOUT rebooting the Power Panel, for example by directly calling batch file UPDMTCX.BAT.

2. Exit
Ausstieg in die Shell (MS-DOS).


4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.12 / 2010-07-02
----------------------------------------------------------------

Contents:
0019#0.fp 01.07 NEW
0019#0.fw 01.17
MTCXSVC.EXE 05.23 NEW
PPHOTFIX.EXE 01.00
LIESMICH.TXT 01.12 NEW
README.TXT 01.12 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- FPGA (0019#0.fp): Bugfix internal keyboard.
Sporadically it can happen during fast key presses, that the
internal keyboard controller will hang. Problem only occurs
in combination with a installed KCF file (KeyboardConfiguration
File) and with MTCX FPGA version V01.06. The internal key and
LED matrix and also a connected USB-keyboard is not affected
with this problem (problem will not occur on Automation Runtime
devices).

Changes:
- MTCXSVC:
- Functional enhancements for PP300/400 and PPC300 series.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.11 * DOS 03/05/2010 158 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0111.zip
Açıklama Firmware Upgrade (MTCX)

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.
(Alternatively, a bootable CompactFlash card or a bootable USB stick can be used. Detailed information can be found in the PP300/400 User Manual)

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:


1. Update MTCX Firmware (PX32/FPGA)
The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards and must be sent to B&R for repair. Retry the aborted update process WITHOUT rebooting the Power Panel, for example by directly calling batch file UPDMTCX.BAT.

2. Exit
Ausstieg in die Shell (MS-DOS).


4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.11 / 2010-02-24
----------------------------------------------------------------

Contents:
0019#0.fp 01.06 NEW
0019#0.fw 01.17
MTCXSVC.EXE 05.21 NEW
PPHOTFIX.EXE 01.00
LIESMICH.TXT 01.11 NEW
README.TXT 01.11 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- FPGA (0019#0.fp): Bugfix serial UART (COM1). Faulty or missing TX data can sporadically occur, when using a high baudrate (e.g. 115200Baud).
- FPGA (0019#0.fp): Bugfix in the power-on sequence of the display backlight. Sporadically it can happen with a 5,7in TFT color QVGA and a 10,4in TFT color VGA display, that a slight display flickering is visible during the first 10 seconds with a cold backlight (problem seems to be only present on newer lot numbers of this display type).

Changes:
- MTCXSVC:
- Support for APC800 Series.
- Support for APC820 Series.
- Support for Display Inverter Update.
- Support for Atom N270 CPU der APC620/PPC700 Series.
- Support for Atom N270 CPU der APC800 Series.
- Support for PPC800 Series.
- Functional enhancements for PP300/400 series.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.10 * DOS 04/30/2008 150 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0110.zip
Açıklama Firmware Upgrade (MTCX)

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.
2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.
3. A boot menu with following options is shown after booting:


1. Update MTCX Firmware (PX32/FPGA)
The MTCX Firmware FPGA and PX32 will be upgraded automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards and must be sent to B&R for repair. Retry the aborted update process WITHOUT rebooting the Power Panel, for example by directly calling batch file UPDMTCX.BAT.

2. Exit
Ausstieg in die Shell (MS-DOS).


4. Select the desired action.
5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.10 / 2008-04-30
----------------------------------------------------------------

Contents:
0019#0.fp 01.03
0019#0.fw 01.17 NEW
MTCXSVC.EXE 03.02
PPHOTFIX.EXE 01.00
LIESMICH.TXT 01.10 NEW
README.TXT 01.10 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- FPGA (0019#0.fp): Bugfix for booting with aPCI modules and without battery, caused by a timing error sometimes the display was not switched on correctly.

Changes:
- None.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.09 * DOS 03/25/2008 150 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0109.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Update MTCX Firmware (PX32/FPGA)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).

----------------------------------------------------------------
Version 01.09 / 2008-03-19
----------------------------------------------------------------

Contents:
0019#0.fp 01.03 NEW
0019#0.fw 01.16
MTCXSVC.EXE 03.02
PPHOTFIX.EXE 01.00
LIESMICH.TXT 01.09 NEW
README.TXT 01.09 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- FPGA (0019#0.fp): Bugfix in the power-on sequence, sporadic
display switch-on problems with FPGA V1.02 are fixed.

Changes:
- FPGA (0019#0.fp): Optimized backlight regulation.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.08 * DOS 01/22/2008 151 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0108.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Update MTCX Firmware (PX32/FPGA)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.08 / 2008-01-22
----------------------------------------------------------------

Contents:
0019#0.fp 01.02
0019#0.fw 01.16 NEW
MTCXSVC.EXE 03.02
PPHOTFIX.EXE 01.00
LIESMICH.TXT 01.08 NEW
README.TXT 01.08 NEW
CONFIG.SYS
AUTOEXEC.BAT
UPDMTCX.BAT

Fixes:
- PX32 (0019#0.fw): Bugfix in handling BIOS profiles.

Changes:
- BIOS: Bugfix in the key emulation, problems with Scancodes for
keys F13-F20 are now fixed.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.07 * DOS 12/17/2007 151 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0107.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Update MTCX Firmware (PX32/FPGA)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.07 / 2007-12-17
----------------------------------------------------------------

Contents:
0019#0.fw 01.15
0019#0.fp 01.02 NEW

Fixes:
- FPGA (0019#0.fp): Bugfix in the PP400 aPCI handling with
combinations of various aPCI modules (IF779 and IF762), module
detection and boot problems are fixed.

Changes:
- FPGA (0019#0.fp): Modification in the RS232 implementation,
a configuration of 2 stop bits will force to accept data
starting with the first stop bit, the second will be ignored
now.
- FPGA (0019#0.fp): Optimizations in the range of NMI masking,
companion chip reset handling and internal memory timing.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.06 * DOS 10/29/2007 149 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0106.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Update MTCX Firmware (PX32/FPGA)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


------------------------------------------------------------------
Version 01.06 / 2007-10-29
------------------------------------------------------------------

Contents:
0019#0.fw 01.15 NEW
0019#0.fp 01.01 NEW

Fixes:
- FPGA (0019#0.fp): Bugfix in the backlight regulation, display
flicker problems with 5.7" up to 12.1" panels are fixed.
- FPGA (0019#0.fp): Bugfix in the PP400 aPCI handling, reset
problems in combination with booting aPCI modules are fixed.
- PX32 (0019#0.fw): Bugfix in the power-on sequence, problems
with short powerfail events stopping in Standby mode are fixed.

Changes:
- PX32 (0019#0.fw): Implementation for supporting BIOS Profiles.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.05 * DOS 08/09/2007 147 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0105.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Update MTCX Firmware (PX32/FPGA)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.05 / 2007-08-08
----------------------------------------------------------------

Contents:
0019#0.fw 01.14 NEW

Fixes:
- BIOS: Bugfix in the key emulation, problems with keyboard
entries are now fixed.

Changes:
- None.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.04 * DOS 06/11/2007 146 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0104.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Update MTCX Firmware (PX32/FPGA)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.04
----------------------------------------------------------------

Contents:
0019#0.fp 01.00 NEW
0019#0.fw 01.13 NEW
MTCXSVC.EXE 3.02 NEW
PPHOTFIX.EXE 1.00 NEW
AUTOEXEC.BAT NEW

Fixes:
- FPGA (0019#0.fp): Power management and backlight regulation
implemented.
- PX32 (0019#0.fw): Power management and backlight regulation
implemented.

Changes:
- MTCXSVC.EXE: Newest version.
- AUTOEXEC.BAT: Executing the Power Panel hotfix tool.
- PPHOTFIX.EXE: New Power Panel hotfix tool.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.03 * DOS 03/12/2007 137 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0103.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Update MTCX Firmware (PX32/FPGA)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.03
----------------------------------------------------------------

Contents:
0019#0.fw 01.12 NEW
MTCXSVC.EXE 3.01 NEW
CONFIG.SYS NEW
UPDMTCX.BAT NEW

Fixes:
- PX32 (0019#0.fw): Contrast regulation for LCD displays.

Changes:
- MTCXSVC.EXE: Newest version.
- CONFIG.SYS: Text optimizations for QVGA devices.
- UPDMTCX.BAT: Text optimizations for QVGA devices.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.02 * DOS 02/23/2007 132 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0102.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Upgrade MTCX Firmware FPGA and PX32 (PP3F/PP3P)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.02
----------------------------------------------------------------

Contents:
0019#0.fw 01.10 NEW
0019#0.fp 00.06 NEW

Fixes:
- FPGA (0019#0.fp): Bugfix in the UART emulation of the serial
COM ports.
- PX32 (0019#0.fw): Bugfix in the contrast configuration for LCD
devices. The values are now interpreted in the right way.

Changes:
- FPGA (0019#0.fp): Optimizations for the handling of devices
with keys.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.01 * 12/20/2006 131 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0101.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Upgrade MTCX Firmware FPGA and PX32 (PP3F/PP3P)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.01
----------------------------------------------------------------

Contents:
0019#0.fw 01.09 NEW

Fixes:
- None.

Changes:
- PX32 (0019#0.fw): Productional changes regarding manual battery test, reading Power/Reset buttons, display handling in initial mode and reading NMI status.
Sürüm Dil
İşletim sistemi
Tarih
Boyut
Tip İndirme
1.00 * DOS 12/13/2006 131 KB ZIP PP300_400_BIOS_MTCX_Firmware_Upgrade_Disk_V0100.zip
Açıklama Firmware Upgrade (MTCX)

----------------------------------------------------------------
GENERAL INFORMATION
----------------------------------------------------------------

With this disk you can update the MTCX firmware for FPGA and PX32 (PP3F/PP3P) on a B&R Power Panel 300/400.

----------------------------------------------------------------
UPDATE PROCEDURE
----------------------------------------------------------------

1. Copy all files to a bootable disk.

2. Insert the disk in a (USB) floppy drive connected to the Power Panel and re-boot the device.

3. A boot menu with following options is shown after booting:

1. Upgrade MTCX Firmware FPGA and PX32 (PP3F/PP3P)

The MTCX Firmware FPGA and PX32 will be upgraded
automatically (Default after 5 sec).

*************************************
Do not abort a MTCX Firmware upgrade!
*************************************

Otherwise the Power Panel cannot be rebooted afterwards
and must be sent to B&R for repair. Retry the aborted
update process WITHOUT rebooting the Power Panel, for
example by directly calling batch file UPDMTCX.BAT.

2. Exit

Ausstieg in die Shell (MS-DOS).

4. Select the desired action.

5. Remove disk and reboot device (after successful update only!).


----------------------------------------------------------------
Version 01.00
----------------------------------------------------------------

Contents:
0019#0.fp 00.05 NEW
0019#0.fw 01.07 NEW
MTCXSVC.EXE 2.11 NEW

Fixes:
- PX32 (0019#0.fw): DPR register wrong, collisions between Board
Config and NMI mask register.
- FPGA (0019#0.fp): Bugfix in NVRAM handling
- MTCXSVC.EXE: A error during programming the last block could
cause a checksum error.
- MTCXSVC.EXE: Bugfix with aPCI module dependant problems during
programming and verify.

Changes:
- PX32 (0019#0.fw): Productional changes regarding manual
battery test.
- FPGA (0019#0.fp): New LCD-B/W Support
- MTCXSVC.EXE: New LPC bus detection.