Input
|
Resistance measurement with constant current supply for 4-wire connections
|
Digital converter resolution
|
24-bit
|
Filter time
|
Configurable between 1 ms and 400 ms
|
Conversion time
|
|
1000 Hz filter
|
1 ms for all inputs
|
50 Hz filter
|
20 ms for all inputs
|
Conversion procedure
|
Sigma-delta
|
Output format
|
DINT or UDINT for resistance measurement
|
Temperature measurement range
|
-200 to 850°C
|
Resistance measurement range
|
0.5 to 390 Ω
|
Temperature sensor resolution
|
1 LSB = 0.001°C
|
Resistance measurement resolution
|
0.001 Ω
|
Input filter
|
First-order low-pass filter / cutoff frequency 1050 Hz
|
Sensor standard
|
EN 60751
|
Insulation voltage between channel and bus
|
500 Veff
|
Insulation voltage between channel and channel
|
500 Veff
|
Linearization method
|
Internal
|
Measurement current
|
1 mA
|
Temperature sensor normalization
|
-200.0 to 850.0°C
|
Reference
|
1568 Ω ±0.1%
|
Permissible input signal
|
Short-term max. 28.8 V
|
Max. error at 25°C
|
|
Gain
|
0.0059%
|
Offset
|
0.0015%
|
Max. gain drift
|
<0.00065%/°C
|
Max. offset drift
|
<0.000025%/°C
|
Nonlinearity
|
<0.001%
|
Standardized range of values for resistance measurement
|
0.5 Ω to 390 Ω
|
Temperature measurement monitoring
|
|
Range undershoot
|
0x80000001
|
Range overshoot
|
0x7FFFFFFF
|
Open circuit
|
0x7FFFFFFF
|
General fault
|
0x80000000
|
Open inputs
|
0x7FFFFFFF
|
Resistance measurement monitoring
|
|
Range undershoot
|
0x80000001
|
Range overshoot
|
0xFFFFFFFF
|
Open circuit
|
0xFFFFFFFF
|
General fault
|
0x80000000
|