    Interfaces1x CAN I/O slave
    Analog channels4 inputs (2 of these can be configured for temperature and resistance measurement), 4 outputs
    Power supply24 VDC
    Status indicatorsI/O function for each channel, status
    Diagnostics
    CAN interfaceYes, with status LED
    I/O functionYes, with LEDs
    Power consumption5 W
    Electrical isolation
    Analog - AnalogNo
    CAN - Digital/AnalogYes
    Digital - DigitalNo
    Digital - AnalogYes
    Certifications
    CEYes
    ULcULus E115267
    Industrial control equipment
    GOST-RYes
    User interface
    Design12-pin multipoint plug
    FieldbusCAN I/O slave
    Max. baud rate500 kbit/s
    Quantity8
    Nominal voltage24 VDC
    Input filter
    Hardware≤ 2 ms
    Software-
    Input circuitSink
    Additional functionsEvent counting, incremental encoder operation, gate, frequency and period measurement
    Input±10 V
    Digital converter resolution12-bit + sign
    Conversion time≤ 5 ms for all channels
    Output formatINT
    Input impedance in signal range20 MΩ
    Input protectionProtection against wiring with supply voltage
    Basic accuracy±0.071% at 25°C
    Based on the current measurement value
    Output formatINT
    Digital converter resolution12-bit
    Input protectionProtection against wiring with supply voltage
    Basic accuracy±0.35% at 25°C
    Based on the current measurement value
    Measurement procedureResistance measurement with constant current feed for 2 wires
    Conversion time≤ 5 ms for all channels
    Resistance measurement range0 to 4000 Ω
    Sensor
    NoteCan be configured for each channel using software
    KTY10-6-50 to 125°C
    PT1000-200 to 850°C
    Output formatINT
    Digital converter resolution12-bit
    Input0 to 4000 Ω
    Input protectionProtection against wiring with supply voltage
    Basic accuracy±0.35% at 25°C
    Based on the current measurement value
    Measurement procedureResistance measurement with constant current feed for 2 wires
    Conversion time≤ 5 ms for all channels
    Quantity8
    Nominal voltage24 VDC
    Total nominal current9.6 A
    Output circuitSource
    Output protectionThermal cutoff for overcurrent or short circuit,
    Integrated protection for switching inductances
    Sensor power supplyExternal
    Additional functionsPulse width modulation
    Nominal output current
    Outputs 1 - 40.4 A
    Outputs 5 - 82.0 A
    Output±10 V
    Digital converter resolution12-bit
    Conversion time≤ 5 ms for all channels
    Switch on/off behaviorInternal enable relay for booting and errors
    Output protectionProtection against wiring with supply voltage, short circuit protection
    Basic accuracy±0.088% at 25°C
    Based on the current output value.
    Degree of protection per EN 60529IP20
    Temperature
    Operation0 to 50°C
    Storage-25 to 70°C
    Relative humidity
    Operation5 to 95%
    NoteOrder 1x TB712 terminal block separately
    Order 2x TB718 terminal blocks separately
    InstallationOn EN50022 compliant mounting rails or screw mounting
    Dimensions
    Width170 mm
    Height80 mm
    Depth30 mm
    Weight410 g

7CX436.50-1

  • 8 digital inputs with special functions (event counting, incremental encoder operation, gate, frequency and period measurement)
  • 8 digital outputs (2 outputs with pulse width modulation)
  • 4 analog inputs (2 inputs for temperature measurement can be used with KTY10 or PT1000)
  • 4 analog outputs
-
Product description:
Material number:
7CX436.50-1
Description:
Remote input/output module, 24 VDC, 1 CAN interface, electrically isolated, network-capable, 8 digital inputs 24 VDC, sink, 2 event counters or 1 incremental encoder or 1 gate time/period duration measurement, 4 digital outputs 0.4 A, 4 digital outputs 2 A, 24 VDC, 2 digital outputs with PWM functionality, 4 analog inputs, ±10 V, 12-bit + sign, two of the analog inputs can be used as KTY10 or PT1000 input, 4 analog outputs, ±10 V, 12-bit, order 2x TB718 and 1x TB712 terminal block separately.
Terminal blocks
  • 7TB712.9

    Accessory terminal block, 12-pin, screw clamps 1.5 mm²

  • 7TB712.91

    Accessory terminal block, 12-pin, cage clamp terminal block 1.5 mm²

  • 7TB718.9

    Accessory terminal block, 18-pin, screw clamps 1.5 mm²

  • 7TB718.91

    Accessory terminal block, 18-pin, cage clamp terminal block 1.5 mm²

Miscellaneous
Terminal blocks
  • 7TB722.9

    2003 terminal block, 22-pin, screw clamps

  • 7TB722.91

    2003 terminal block, 22-pin, cage clamps

  • 7TB733.9

    2003 terminal block, 33-pin, screw clamps

  • 7TB733.91

    2003 terminal block, 33-pin, cage clamps

  • 7TB736.9

    2003 terminal block, 36-pin, screw clamps

  • 7TB736.91

    2003 terminal block, 36-pin, cage clamps

  • 7TB772.91

    2003 terminal block, 72-pin, cage clamps

отметить все
Share
This site uses cookies to enable a better customer experience. By continuing to browse the site you are agreeing to our use of cookies. Please find more information about cookies in our Политика конфиденциальности.