Short description
I/O module 2x M12 interface each with 2 safe type A digital inputs and 2 pulse outputs, 24 VDC,
2x standardized 8-pin M12 device interface each with 1 digital input without safety function and 2 safe type A digital inputs and 2 pulse outputs, 24 VDC and 1 digital output without safety function, 24 VDC, 0.6 A and 1 device power supply, 24 VDC, 2 A
General information
B&R ID code 0xBB7C
System requirements
Automation Studio 3.0.81.15 or later
Automation Runtime 3.00 or later
SafeDESIGNER 2.70 or later
Safety Release 1.2 or later
mapp Technology Package mapp Safety 5.7.0 or later
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
I/O function Yes, using LED status indicator and software
Blackout mode
Scope Module
Function Module functionality
Standalone mode No
Max. I/O cycle time 1 ms
Connection type
X2X Link M12, B-coded
Inputs/Outputs M12 8-pin or M12 5-pin, A-coded
I/O power supply M8, 4-pin
Power consumption
Bus 0.9 W
Internal I/O 2.1 W
Additional power dissipation caused by actuators (resistive) [W]
Digital outputs 0.216
Pulse outputs 0.192
Electrical isolation
Channel - Bus Yes
Channel - Channel No
Certifications
CE Yes
UKCA Yes
Functional safety cULus FSPC E361559
Energy and industrial systems
Certified for functional safety
ANSI UL 1998:2013
Functional safety IEC 61508:2010, SIL 3
EN 62061:2005/A2:2015, SIL 3
EN ISO 13849-1:2015, Cat. 4 / PL e
IEC 61511:2004, SIL 3
Functional safety EN 50156-1:2004
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
Safety characteristics
EN ISO 13849-1:2015
Category Cat. 3 when using individual input channels,
Cat. 4 when using input channel pairs (e.g. SI1 and SI2) or more than 2 input channels
PL PL e
DC >94%
Mission time Max. 20 years
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
SIL CL SIL 3
SFF >90%
PFH / PFHd
openSAFETY wired Negligible
openSAFETY wireless <1*10-14 * Number of openSAFETY packets per hour
Proof test interval (PT) 20 years
Safe digital inputs
EN ISO 13849-1:2015
MTTFD per channel 100 years when using individual input channels,
2500 years when using input channel pairs (e.g. SI1 and SI2) or more than 2 input channels
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
PFH / PFHd per channel <1*10-10
PFD per channel <2*10-5
24 VDC output
Output voltage 24 VDC -15% / +20%
Output current 2 A
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Digital inputs
Quantity 2
Nominal voltage 24 VDC
Input characteristics per EN 61131-2 Type 1
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Min. 2 mA to max. 7.24 mA
Input circuit Sink
Input filter
Hardware ≤150 μs
Input resistance Min. 3.3 kΩ
Switching threshold
Low <5 VDC
High >15 VDC
Insulation voltage between channel and bus 500 Veff
Safe digital inputs
Quantity 8
Variant Type A
Nominal voltage 24 VDC
Input characteristics per EN 61131-2 Type 1
Input filter
Hardware ≤150 μs
Software Configurable between 0 and 500 ms
Input circuit Sink
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Min. 2 mA to max. 8.28 mA
Input resistance Min. 2.9 kΩ
Error detection time 200 ms
Insulation voltage between channel and bus 500 Veff
Switching threshold
Low <5 VDC
High >15 VDC
Line length between signal source (pulse output or external signal) and input Max. 60 m with unshielded line
Max. 400 m with shielded line
Digital outputs
Quantity 2
Variant FET, positive switching, output level readable
Nominal voltage 24 VDC
Switching voltage I/O power supply minus voltage drop due to RDS(on)
Max. switching frequency See section "Inrush current behavior for output channels".
Nominal output current 0.6 A
Total nominal current 1.2 A
Output protection See section "Inrush current behavior for output channels".
Leakage current when the output is switched off <500 μA
RDS(on) 300 mΩ
Peak short-circuit current See section "Inrush current behavior for output channels".
Braking voltage when switching off inductive loads 50 VDC
Insulation voltage between channel and bus 500 Veff
Max. capacitive load 100 nF
Peak output current 1 A
Pulse outputs
Quantity 8
Variant Push-Pull
Nominal output current 40 mA
Output protection Shutdown of individual channels in the event of overload or short circuit
Peak short-circuit current 25 A for 15 µs
Short-circuit current 100 mAeff
Leakage current when the output is switched off 0.1 mA
RDS(on) 60 Ω
Switching voltage I/O power supply minus voltage drop due to RDS(on)
Total nominal current 80 mA
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level 0 to 2000 m, no limitation
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -40 to 60°C
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 190 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Номер модель:
X67SI8103
Описание:
  • 8 safe digital inputs, sink circuit
  • 2 pulse outputs - available on all 4 female connectors
  • 2 standard inputs, sink circuit
  • 2 standard outputs, source circuit
  • Device supply
  • Software input filter configurable for each channel
  • Standardized 8-pin M12 device interface

This module is equipped with 8 safe digital inputs. They are designed for a nominal voltage of 24 VDC.

The module can be used to read various digital signals in safety-related applications up to PL e or SIL 3.

The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.

M-CAD (Механические Шаблоны Версия (Дата) Загрузка
3D file DFX/STEP X67SI8103 ZIP / 3 MB
Документация Версия (Дата) Загрузка
Data sheet X67SI8103 - Legacy PDF / 2 MB
Data sheet X67SI8103 - mapp Safety PDF / 1 MB
Installation- / EMC-Guide PDF / 20 MB
X67 System User´s Manual PDF / 6 MB
Инструменты / Утилиты / Примеры Версия (Дата) Загрузка
Sistema library ZIP / 336 KB
Обновление Automation Studio HW Версия (Дата) Загрузка
V3.0 HW Upgrade (X67SI8103) EXE / 3 MB
V4.0 HW Upgrade (X67SI8103) EXE / 3 MB
V4.6 HW Upgrade (X67SI8103) EXE / 2 MB
V6.0 HW Upgrade (X67SI8103) EXE / 2 MB
Сертификаты Версия (Дата) Загрузка
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X67 PDF / 155 KB
EU Declaration FS PLC X67 PDF / 230 KB