Por favor selecione país e idioma

Short description
System module Power supply of 4 potentiometers with ±10 V
General information
B&R ID code 0x1F43
Status indicators Potentiometer power supply monitoring per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Open circuit Yes, using LED status indicator and software
Overload Yes, using LED status indicator and software
Power consumption
Bus 0.01 W
Internal I/O 1.8 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV GL Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
ABS Yes
EAC Yes
KC Yes
Potentiometer power supply
Number of power supplies 4
Voltage ±10 V
Potentiometer resistance 1 kΩ to 10 kΩ
Load Max. 20 mA per power supply channel
Short-circuit proof Yes
Basic accuracy
+10 V ±0.12% at 25°C
-10 V ±0.21% at 25°C
20 V ±0.165% at 25°C
Insulation voltage between channel and bus 500 Veff
Max. drift
+10 V ±0.00012 %/°C
-10 V ±0.00032 %/°C
20 V ±0.00022 %/°C
Electrical properties
Electrical isolation
Channel isolated from bus

Channel not isolated from channel
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.
Pitch 12.5+0.2 mm
Material number:
X20PS4951
Description:
  • Open circuit and short circuit detection
  • Simple implementation of potentiometer inputs
  • 4x supply

In order to connect potentiometers, modules must first be supplied with the appropriate voltage. The potentiometer supply module can be used to supply four potentiometers with ±10 V. The data is evaluated using standard analog input modules.

Mandatory Accessories
Bus modules
X20BM11 X20 bus module, 24 VDC keyed, internal I/O power supply connected through
X20BM15 X20 bus module, with node number switch, 24 VDC keyed, internal I/O power supply connected through
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Automation Studio HW Upgrades Version (Date) Download
V2.6 HW Upgrade (X20PS4951) EXE / 914 KB
V3.0 HW Upgrade (X20PS4951) EXE / 1 MB
V4.0 HW Upgrade (X20PS4951) EXE / 620 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
ABS Certificate of Product Design Assessment - X20 IO Series PDF / 2 MB
DNV Type Approval Certificate - X20 PDF / 192 KB
E115267 UL CoC X20 PDF / 847 KB
FTZU 09 ATEX 0083X PDF / 771 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Lloyds Register PDF / 506 KB
RINA Type Approval Certificate - X20 / Power Panel T30 PDF / 1 MB
X20, X67 KC certificates PDF / 6 MB
Documentation Version (Date) Download
Data sheet X20PS4951 PDF / 191 KB
X20 System User´s Manual PDF / 56 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 177 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Por favor selecione país e idioma

B&R Logo

Please choose country

B&R Logo

Please choose country

B&R Logo