Short description
Hub 2-port Fast Ethernet hub for redundant wiring
General information
Status indicators Module status, bus function
Diagnostics
Module status Yes, using LED status indicator
Bus function Yes, using LED status indicator
Power consumption 1.17 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
EAC Yes
KC Yes
Interfaces
Type Active hub expansion module
Variant 2x shielded RJ45
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex No
Autonegotiation Yes
Auto-MDI/MDIX Yes
Hub propagation delay 0.96 to 1 µs
Electrical properties
Electrical isolation Power supply isolated from Ethernet (IF1 and IF2)
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Slot Hub expansion for X20BC8084 and X20HB8884
Materiaalnummer:
X20HB2885
Omschrijving:
  • Active hub expansion module
  • 2x Fast Ethernet hub for redundant wiring
  • Hot-swap-capable

The X20BC8084 POWERLINK bus controller and the X20HB8884 module are equipped with an integrated link selector function. An additional 1 or 2 slots are available, depending on the bus base used. The active X20HB2885 hub expansion module can be operated in these slots.

The active hub expansion module is equipped with one integrated 2x hub and allows redundant wiring. This means that the connection between the two ports remains intact if there is a failure in the bus controller or Compact Link Selector. The status of the module and network are indicated by LEDs.

Meer informatie:

Technology information: Redundancy

User's manual: Redundancy for control systems

Vereiste toebehoren
Expandable bus controllers
X20BC8084 X20 bus controller, 1 POWERLINK interface, 1x link selector for POWERLINK cable redundancy, supports expansion with active X20 hub modules, 2x RJ45, order bus base, power supply module and terminal block separately!
System modules for expandable bus controllers
X20BB82 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, with 2 expansion slots for 2 X20 add-on modules (IF, HB, etc.), X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20 redundancy systems
X20HB8884 X20 Compact link selector, 2x RJ45, order bus base, power supply module and terminal block separately!
Automation Studio HW Upgrades Versie (Datum) Download
V4.0 HW Upgrade (X20HB2885) EXE / 660 KB
Certificaten Versie (Datum) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
DNV Type Approval Certificate - X20 PDF / 194 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB
Documentatie Versie (Datum) Download
Data sheet X20(c)HB2885 PDF / 160 KB
Installation- / EMC-Guide PDF / 20 MB
Redundancy for control systems PDF / 9 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Electro of EPLAN Templates) Versie (Datum) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. Templates) Versie (Datum) Download
3D File STEP/DXF X20 Module ZIP / 1 MB