General information
Status display | Green LED on front |
Terminals | Stable screw clamp terminal blocks |
Certifications |
Terminal block
Connection cross section | |
Flexible | 0.5 to 4 mm² / 20 to 10 AWG |
Inflexible | 0.5 to 6 mm² / 20 to 10 AWG |
Input
Input voltage |
AC 85-132 / 176-264 V (switchable), 47-63 Hz DC 240-375 V |
Input current | <6 A (switch position 115 V) <BR/><2.8 A (switch position 230 V) |
External fuse protection |
Not required, device equipped with internal fuse Recommendation: Fuse the power supply cable (circuit breaker). |
Transient immunity | Transient-proof per VDE 0160 / W2 |
Output (including logic)
Output noise suppression | Device complies with EN 61000-6-3 (class B) |
Output power | 240 W |
Nominal voltage | 24 to 28 VDC (default setting: 24.5 V ±0.5%) |
Power back immunity | 34 V |
Protection functions | Output is short-circuit, overload- and no-load proof. |
Overvoltage protection | Typ. 35 V |
Permissible output load | |
TU = 0 to 45°C | 12 A / 24 V or 10.3 A / 28 V (288 W) |
TU = 0 to 60°C | 10 A / 24 V or 8.6 A / 28 V (240 W) |
Efficiency, reliability
Efficiency | Typ. 90% (230 VAC, 24 V / 10 A) |
MTBF | 425,000 h |
Losses | Typ. 26.7 W (230 VAC, 24 V / 10 A) |
Ambient conditions
Temperature | |
Operation | 0 to 70°C |
Storage | -25 to 85°C |
Relative humidity | |
Operation | Max. 95% |
Mechanical properties
Installation | Easy snap-on mounting onto the top-hat rail |
Dimensions | |
Width | 120 mm |
Height | 124 mm |
Depth | 102 mm (plus top-hat rail) |
Weight | 980 g |
Ventilation/Cooling | Normal convection, no fan required |
型番:
0PS110.1説明:
24 VDC power supply unit, 1-phase, 10 A, input 115/230 VAC, manual select, top-hat rail installation
ドキュメンテーション | バージョン (日付) | ダウンロード |
---|---|---|
Datasheet 0PS110.1 | PDF / 734 KB |