Short description
Potential distributor module 5x 24 VDC on the terminal connections, 5x ground on the terminal connections
General information
B&R ID code 0x2680
Status indicators Operating state, module status
Diagnostics
Module run/error Yes, using status LED and software
Fuse monitoring Yes, using status LED and software
Power consumption
Bus 0.12 W
Internal I/O -
External I/O 1.15 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV GL Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
KR Yes
EAC Yes
KC Yes
Input supply
Nominal input voltage 24 VDC -15% / +20% external, external ground
Fuse Integrated 6.3 A, slow-blow, can be replaced
Reverse polarity protection No
Output supply
Nominal output voltage 24 VDC, ground
Permissible contact load 10 A
Behavior on short circuit
On 24 VDC power supply Integrated fuse
On GND power supply No protection available
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Pitch 12.5+0.2 mm
Material number:
X20PD0016
Description:
  • Integrated exchangeable microfuse
  • Monitoring of the fuse
  • Potential for routing as needed
  • Distribution of the load and electronics supply
  • Isolation from the internal I/O supply

The potential distributor module provides 5x 24 VDC and 5x ground connections (from an external supply) at the terminals. There is no connection to the internal I/O supply, so this module only serves to distribute an external supply for the load and electronics supply. The externally fed 24 VDC supply is provided on the terminal connections through a replaceable microfuse. The 24 VDC feed and the functionality of the fuse are monitored.

Mandatory Accessories
Bus modules
X20BM11 X20 bus module, 24 VDC keyed, internal I/O supply continuous
X20BM15 X20 bus module, with node number switch, 24 VDC keyed, internal I/O supply continuous
Terminal blocks
X20TB12 X20 Connettore 12 poli
Automation Studio HW Upgrades Version (Date) Download
V2.6 HW Upgrade (X20PD0016) EXE / 1 MB
V3.0 HW Upgrade (X20PD0016) EXE / 1 MB
V4.0 HW Upgrade (X20PD0016) EXE / 682 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
DNV GL Type Approval Certificate - X20 / Power Panel T30 PDF / 164 KB
E115267 UL CoC X20 PDF / 1 MB
FTZU 09 ATEX 0083X PDF / 697 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Documentation Version (Date) Download
Datasheet X20PD0016 PDF / 173 KB
X20 System User´s Manual PDF / 50 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Please choose country and language

B&R Logo