Short description
I/O module 1 safe type A digital counter channel, 7 kHz, 24 VDC
General information
B&R ID code 0xCAC1
System requirements
Automation Studio 3.0.90 or later
Automation Runtime 3.00 or later
SafeDESIGNER 2.91 or later
Safety Release 1.5 or later
mapp Technology Package mapp Safety 5.7.0 or later
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Inputs Yes, using LED status indicator and software
Blackout mode
Scope Module
Function Module functionality
Standalone mode No
Max. I/O cycle time 2 ms
Power consumption
Bus 0.25 W
Internal I/O 0.75 W
Additional power dissipation caused by actuators (resistive) [W] 0.064
Electrical isolation
Channel - Bus Yes
Channel - Channel No
Certifications
CE Yes
UKCA Yes
Functional safety cULus FSPC E361559
Energy and industrial systems
Certified for functional safety
ANSI UL 1998:2013
Functional safety IEC 61508:2010, SIL 3
EN 62061:2005/A2:2015, SIL 3
EN ISO 13849-1:2015, Cat. 4 / PL e
IEC 61511:2004, SIL 3
Functional safety EN 50156-1:2004
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: A (0 to 45°C)
Humidity: B (up to 100%)
Vibration: A (0.7 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
ABS Yes
BV EC21B
Temperature: 5 - 45°C
Vibration: 0.7 g
EMC: Bridge and open deck
EAC Yes
KC Yes
Safety characteristics
EN ISO 13849-1:2015
Category Cat. 4
The special instructions in chapter "Connection examples" must be taken into account.
PL PL e
DC >94%
MTTFD per channel 2500 years
Mission time Max. 20 years
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
SIL CL SIL 3
SFF >90%
PFH / PFHd per channel <1*10-10
PFH / PFHd
openSAFETY wired Negligible
openSAFETY wireless <1*10-14 * Number of openSAFETY packets per hour
PFD per channel <2*10-5
Proof test interval (PT) 20 years
Encoder power supply
Output voltage I/O power supply minus voltage drop due to RDS(on)
Nominal output current 80 mA
RDS(on) 10 Ω
Protective measures
Short-circuit proof Thermal limit determined by PTC
I/O power supply
Nominal voltage 24 VDC
Voltage range 24 VDC -15% / +20%
Integrated protection Reverse polarity protection
Safe digital counter inputs
Quantity 1
Variant Type A
Nominal voltage 24 VDC
Input characteristics per EN 61131-2 Type 1
Input filter
Hardware <10 µs
Software Configurable between 0 and 100 s
Input frequency Max. 7 kHz
Input circuit Sink
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Min. 2 mA to max. 2.48 mA
Input resistance 9.68 kΩ
Insulation voltage between channel and bus 500 Veff
Switching threshold
Low <5 VDC
High >15 VDC
Line length Max. 30 m shielded
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level 0 to 2000 m, no limitation
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation 0 to 60°C
Vertical mounting orientation 0 to 50°C
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x safety-keyed terminal block separately.
Order 1x safety-keyed bus module separately.
Pitch 25+0.2 mm
Référence produit:
X20SD1207
Description:
  • 1 safe digital counter input with up to 7 kHz counter frequency
  • For encoder inputs A-A, A-B, A-A/-B-B/
  • Sink circuit
  • Input filter configurable

This module is equipped with 1 safe digital input for determining the velocity. Velocity information can be acquired from AB signals up to a maximum frequency of 7 kHz.

The safe counter module is suitable for safely acquiring velocities for safety-related applications up to PL e or SIL 3.

This module is designed for X20 12-pin terminal blocks.

Accessoires obligatoires
Bus modules
X20BM33 X20 bus module, for X20 SafeIO modules, internal I/O power supply connected through
X20BM36 X20 bus module, for X20 SafeIO modules, with node number switch, internal I/O power supply connected through
Terminal blocks
X20TB52 X20 terminal block, 12-pin, safety-keyed
Automation Studio HW Upgrades Version (date) Téléchargement
V3.0 HW Upgrade (X20SD1207) EXE / 1 Mo
V4.0 HW Upgrade (X20SD1207) EXE / 2 Mo
V4.6 HW Upgrade (X20SD1207) EXE / 888 Ko
Certifications Version (date) Téléchargement
244665 CSA HazLoc CoC X20, X67 PDF / 158 Ko
ABS Certificate of Product Design Assessment - X20 IO Series PDF / 2 Mo
BV Type Approval Certificate - X20 PDF / 556 Ko
DNV Type Approval Certificate - X20 PDF / 194 Ko
E115267 UL CoC X20 PDF / 1 Mo
EU Declaration FS PLC X20 PDF / 210 Ko
FS Certificate SafeDESIGNER, SafeLOGIC, SafeIO PDF / 878 Ko
FS Certificate mapp Safety PDF / 974 Ko
FS EN 50156 Zertifikat SafeLOGIC, SafeIO PDF / 314 Ko
FTZU 09 ATEX 0083X PDF / 771 Ko
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 Ko
Lloyds Register PDF / 502 Ko
RINA Type Approval Certificate - X20 / Power Panel T30 PDF / 1 Mo
UK Declaration FS PLC X20 PDF / 112 Ko
X20, X67 KC certificates PDF / 6 Mo
Documentation Version (date) Téléchargement
Data sheet X20(c)SD1207 - Legacy PDF / 1 Mo
Data sheet X20(c)SD1207 - mapp Safety PDF / 1 Mo
Installation- / EMC-Guide PDF / 20 Mo
X20 System User´s Manual PDF / 7 Mo
E-CAD (modèles Electro ou EPLAN) Version (date) Téléchargement
X20 EPLAN P8 from V2.4 EXE / 160 Mo
M-CAD (modèles mécaniques) Version (date) Téléchargement
3D file STEP X20(c)Sxxxxx - Terminal block right side ZIP / 21 Ko
DFX File I/O Slice ZIP / 4 Ko
Dimensions PDF X20 I/O Slice PDF / 45 Ko
Outils / Utilitaires / Exemples Version (date) Téléchargement
Sistema library ZIP / 336 Ko

Veuillez sélectionner un pays et une langue