Short description
Bus receiver | CAN I/O slave |
General information
B&R ID code | 0xEBED |
Status indicators | Module status, bus function, data transfer, I/O power supply, bus power supply |
Diagnostics | |
Module status | Yes, using LED status indicator |
Bus function | Yes, using LED status indicator |
Data transfer | Yes, using LED status indicator |
Overload | Yes, using LED status indicator and software |
Power consumption for X2X Link power supply | 0.6 W |
Power consumption | |
Internal I/O | 0.6 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
EAC | Yes |
X2X Link and I/O power supply
Input voltage | 24 VDC -15% / +20% |
Fuse |
Required line fuse: Max. 16 A, slow-blow for wiring Integrated fuse for module, non-replaceable |
Reverse polarity protection | Yes |
X2X Link power supply output
Output I/O power supply
Nominal output voltage | 24 VDC |
Behavior on short circuit | Required line fuse |
Permissible contact load | 10 A |
Interfaces
Electrical properties
Electrical isolation |
X2X Link supply not isolated from X2X Link power supply I/O supply not isolated from I/O power supply CAN I/O not isolated from I/O or X2X Link power supply |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB12 separately. Order 1x power supply bus module X20BM01 separately, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included. |
Pitch | 12.5 +0.2 mm |

Material number:
X20BR7300Description:
- Fieldbus: CAN bus
- Automatic firmware update via the fieldbus
- Integrated I/O access in B&R Automation Studio
The bus receiver makes it possible to connect X2X Link I/O nodes to CAN I/O. CAN I/O is a transfer protocol based on standard CAN bus that is fully integrated in the B&R system.
Up to 43 logical I/O modules can be connected to the bus receiver. Up to 16 of these can be analog modules.
Mandatory Accessories
Automation Studio HW Upgrades | Version (Date) | Download |
---|---|---|
V4.2 HW Upgrade (X20BR7300) | EXE / 1,006 KB |
Documentation | Version (Date) | Download |
---|---|---|
Data sheet X20BR7300 | PDF / 215 KB | |
X20 System User´s Manual | PDF / 56 MB |
E-CAD (Electro or EPLAN Templates) | Version (Date) | Download |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 161 MB |
M-CAD (Mechan. Templates) | Version (Date) | Download |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 KB | |
3D File STEP X20 I/O-Slice | ZIP / 872 KB | |
Dimensions PDF X20 Electronic module | PDF / 3 KB |