Variant
|
FET positive switching
|
Nominal voltage
|
24 VDC
|
Switching voltage
|
24 VDC -15 % / +20 %
|
Nominal output current
|
0.5 A
|
Total nominal current
|
3 A
|
Connection type
|
1- or 2-wire connections
|
Output circuit
|
Source
|
Output protection
|
Thermal cutoff if overcurrent or short circuit occurs (see value "Peak short circuit current") Internal inverse diode for switching inductive loads (see section "Switching inductive loads")
|
Diagnostic status
|
|
Open circuit
|
Current is <1 mA (typ.): Detected if the output is OFF, delay approx. 10 ms
|
Short circuit to 24 VDC
|
Detected if the output is OFF, delay approx. 10 ms
|
Short circuit to GND
|
Detected if the output is ON, delay approx. 10 ms
|
Overload/Overtemperature
|
Detected if the output is ON, delay approx. 10 ms
|
Leakage current when the output is switched off
|
<160 μA
|
RDS(on)
|
150 mΩ
|
Peak short-circuit current
|
<40 A
|
Switch-on in the event of overload shutdown or short-circuit shutdown
|
Depends on the module temperature
|
Switching delay
|
|
0 → 1
|
<100 μs
|
1 → 0
|
<300 μs
|
Switching frequency
|
|
Resistive load
|
Max. 2000 Hz
|
Inductive load
|
See section "Switching inductive loads"
|
Braking voltage when switching off inductive loads
|
45 to 52 VDC
|
Insulation voltage between channel and bus
|
510 Veff
|