Short description
Interfaces | 1x X2X Link slave |
General information
B&R ID code | 0x17CF |
Power supply | 24 VDC |
Status LED |
Yes (color and blink code) LEDs DI1 to DI8 = State of the digital inputs (green) LEDs DO1 to DO8 = State of the digital outputs (yellow) |
Status indicators | I/O function for each digital channel, status |
Diagnostics | |
Power supply | Yes, using software |
Supply voltage monitoring | The power supply is only enabled starting at an input voltage of approx. 15 V. |
X2X Link interface | Yes, using status LED |
Digital outputs | Yes, using status LED and software |
Power consumption | 5 W |
Electrical isolation | |
24 VDC - Analog | Yes |
24 VDC - Dig. output | No |
24 VDC - Dig. input | Yes |
Analog - Analog | No |
X2X Link - 24 VDC | Yes |
X2X Link - Digital/Analog | Yes |
Digital - Analog | Yes |
Certifications | |
CE | Yes |
UL |
cULus E115267 Industrial control equipment |
Interfaces
User interface | |
Variant | 12-pin multipoint plug |
Type | X2X Link slave |
Differential input
Output format | INT |
Digital converter resolution | 12-bit |
Input |
0 to 10 V Cutoff frequency = 10 kHz Slope = 60 dB |
Input type | Voltage input |
Input filter | 3rd-order low pass / cutoff frequency 10 kHz |
Input impedance in signal range | 20 MΩ |
Input protection | Protection against wiring with supply voltage |
Conversion time | ≤300 µs |
Range of values / Input signal | |
0 VDC | 0x0000 |
10 VDC | 0x7FFF |
Digital inputs
Quantity | 8 |
Nominal voltage | 24 VDC |
Input voltage | 24 VDC ±25% |
Input current at 24 VDC |
Inputs 1 to 3: Approx. 10 mA Inputs 4 to 8: Approx. 5 mA |
Input circuit | Sink or source |
Input filter | |
Hardware |
Inputs 1 to 3: ≤4 µs Inputs 4 to 8: ≤200 µs |
Additional functions | Inputs 1 to 3: Event counting, incremental encoder operation, gate or period measurement |
Switching threshold | |
Low | <5 V |
High | >15 V |
AB incremental encoder
Quantity | 1 |
Counter size | 32-bit |
Input frequency | Max. 30 kHz |
Evaluation | 4x |
Signal form | Square wave pulse |
ABR incremental encoder
Quantity | 1 |
Counter size | 16-bit |
Input frequency | Max. 30 kHz |
Evaluation | 4x |
Signal form | Square wave pulse |
Event counters
Quantity | 2 |
Signal form | Square wave pulse |
Evaluation | Positive or negative edge, cyclic counter |
Input frequency | Max. 100 kHz |
Pulse length | >4 μs |
Counter 1 | Input 1 |
Counter 2 | Input 2 |
Counter size |
Counter 1: 32-bit Counter 2: 16-bit |
Gate measurement
Quantity | 1 |
Signal form | Square wave pulse |
Evaluation | Positive or negative edge |
Counter frequency | |
Internal | 4 MHz or 31.25 kHz |
External | Max. 100 kHz |
Counter size | 32-bit |
Input frequency | Max. 100 kHz |
Length of pause between pulses | >4 μs |
Pulse length | >4 μs |
Supported inputs | Input 1 |
Period measurement
Quantity | 1 |
Signal form | Square wave pulse |
Supported inputs | Input 1 |
Input frequency | Max. 100 kHz |
Evaluation | Positive or negative edge |
Counter size | 32-bit |
Counter frequency | |
Internal | 4 MHz or 31.25 kHz |
External | Max. 100 kHz |
Comparator
Quantity | 1, can be configured using software |
Triggering | Takes place either on digital output 1 or analog output 3 with a predefined value |
Response time | ≤200 µs |
Timestamp for trigger | Yes |
Trigger threshold | Can be used on an analog input |
Trigger threshold for triggering | Yes |
Digital outputs
Quantity | 8 |
Nominal voltage | 24 VDC |
Switching voltage | 24 VDC ±25% |
Nominal output current |
Outputs 1 to 4: 4 A Outputs 5 to 8: 8 A |
Total nominal current |
Outputs 1 to 4: 4 A Outputs 5 to 8: 8 A Per module: 10 A |
Output circuit | Source |
Output protection |
Thermal cutoff for overcurrent or short circuit, integrated protection for switching inductances, reverse polarity protection for output supply |
Switching delay | |
0 → 1 |
Outputs 1 to 4: Typ. 100 µs / Max. 250 µs Outputs 5 to 8: Typ. 70 µs / Max. 150 µs |
1 → 0 |
Outputs 1 to 4: Typ. 100 µs / Max. 270 µs Outputs 5 to 8: Typ. 80 µs / Max. 200 µs |
Switching frequency (resistive load) | Max. 100 Hz |
Sensor power supply | External |
Type | High-side driver (source) |
Additional functions | - |
Analog outputs
Quantity | 3 |
Output | ±10 V |
Digital converter resolution | 12-bit or 11-bit signed??? |
Conversion time | ≤300 µs for all channels |
Switch on/off behavior | Internal enable relay for booting and errors |
Output protection | Protection against wiring with supply voltage, short circuit protection |
Output format | |
Data type | INT |
Voltage | INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV or 0x0010 = 4.882 mV????? |
Range of values | |
10 V | 0x7FFF |
0 V | 0x0000 |
-10 V | 0x8001 |
Max. load per output | ±10 mA (load <1 kΩ) |
Potentiometer, displacement gauge
Input type | Single ended input in the range from 0 to Upot |
Digital converter resolution | 14-bit |
Measurement sensor | 1 to 10 kΩ, potentiometer |
Conversion time | ≤300 µs for all channels |
Output format | INT |
Input protection | Protection against wiring with supply voltage |
Potentiometer supply voltage Upot | 4.5 VDC / Max. 9 mA |
Range of values / Input signal | |
Loop voltage = Upot | 0x7FFF |
Loop voltage = GND | 0x0000 |
Power supply
Voltage range | 24 VDC ±25% |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | 0 to 50°C |
Storage | -25 to 70°C |
Transport | -25 to 70°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x TB712 terminal block separately Order 2x TB718 terminal blocks separately |
Installation | On top-hat rail conforming to EN 50022 or screw mounting |
Weight | 410 g |
Module dimensions including mounting plates | 170 x 80 x 30 mm (H x W x D) |

Material number:
7XX426.50-1Description:
- 8 digital inputs with special functions (event counting, incremental encoder operation, gate and period measurement)
- 8 digital outputs
- 4 analog inputs for potentiometer and displacement gauge
- 1 analog input for voltage measurement
- 3 analog outputs
Mandatory Accessories
Terminal blocks
Optional Accessories
Other
0AC301.9 | Accessory, 8x shielding clamp |
Terminal blocks
7TB722.9 | 2003 terminal block, 22-pin, screw clamps |
7TB722.91 | 2003 terminal block, 22-pin, cage clamps |
7TB733.9 | 2003 terminal block, 33-pin, screw clamps |
7TB733.91 | 2003 terminal block, 33-pin, cage clamps |
7TB736.9 | 2003 terminal block, 36-pin, screw clamps |
7TB736.91 | 2003 terminal block, 36-pin, cage clamps |
7TB772.91 | 2003 terminal block, 72-pin, cage clamps |
Automation Studio HW Upgrades | Version (Date) | Download |
---|---|---|
V2.6 HW Upgrade (7XX426.50-1) | EXE / 428 KB | |
V3.0 HW Upgrade (7XX426.50-1) | EXE / 427 KB |
Documentation | Version (Date) | Download |
---|---|---|
CX / XX Users Manual | PDF / 7 MB | |
Compact I/O User's Manual | PDF / 4 MB |
M-CAD (Mechan. Templates) | Version (Date) | Download |
---|---|---|
3D File STEP 7XX_7CX | ZIP / 791 KB |