Por favor elija país e idioma:

Short description
Interfaces 1x X2X Link slave
General information
Power supply 24 VDC
Status indicators I/O function for each digital output, status
Diagnostics
I/O function Yes, with software status
Power supply Yes, with software status
X2X Link Yes, with status LED
Power consumption 4.0 W
Electrical isolation
24 VDC - Analog Yes
24 VDC - Dig. output No
24 VDC - Dig. input Yes
Dig. inputs - Dig. outputs Yes
X2X Link - 24 VDC Yes
X2X Link - All channels Yes
Digital - Analog Yes
Certifications
CE Yes
UL cULus E115267
Industrial control equipment
GOST-R Yes
Interfaces
User interface
Design 12-pin multipoint plug
Type X2X Link slave
Digital inputs
Quantity 16
Nominal voltage 24 VDC
Input filter
Hardware
Channel 1-3 ≤4 µs
Channel 4-16 ≤200 µs
Software
Channel 1-3 -
Channel 4-16 -
Input circuit
Channel 1-3 Sink
Channel 4-16 Sink or source
Additional functions
Channel 1-3 Event counting, incremental encoder operation, gate, frequency and period measurement
Channel 4-16 -
Analog inputs
Quantity 2
Digital converter resolution 24-bit
Conversion time Configurable between 3 and 20 ms
Output format DINT
Input protection Protection against wiring with supply voltage
Operating range / Measurement sensor 75 to 5000 Ω
Conversion procedure Sigma Delta
Bridge voltage 4.5 VDC / max. 60 mA
Effective resolution 15 to 18-bit (depending on the data output rate and measurement range)
Input current <140 nA
Measurement range Approximately ±8 to ±65 mV, can be configured using software
Type Differential full-bridge strain gauge inputs
Wiring 4-wire
Digital outputs
Quantity 8
Nominal voltage 24 VDC
Total nominal current 10.0 A
Output circuit Source
Output protection Thermal cutoff for overcurrent or short circuit,
integrated protection for switching inductances, reverse polarity protection for output supply
Sensor power supply External
Additional functions -
Nominal output current
Outputs 1 - 4 0.5 A
Outputs 5 - 8 2.0 A
Operating conditions
Degree of protection per EN 60529 IP20
Environmental conditions
Temperature
Operation 0 to 50°C
Storage -25 to 70°C
Relative humidity
Operation 5 to 95%
Mechanical properties
Note Order 1x TB712 terminal block separately
Order 2x TB718 terminal blocks separately
Installation On EN50022 compliant mounting rails or screw mounting
Dimensions
Width 170 mm
Height 80 mm
Depth 30 mm
Weight 405 g
Material number:
7XX415.50-K02
Description:
  • 2 full-bridge strain gauge inputs
  • 8 digital outputs
  • 16 digital inputs with special functions (event counting, incremental encoder operation, gate, frequency and period measurement)
Remote input/output module, 24 VDC, X2X Link, electrically isolated, 2 full-bridge strain gauge inputs, 4 digital outputs 0.5 A, 4 digital outputs 2 A, 24 VDC, 16 digital inputs, 24 VDC, sink/source, 3 event counters or 1 incremental encoder or 1 gate time/period duration measurement and 1 event counter, order 2x 0TB718 and 1x 0TB712 terminal block separately.
Mandatory Accessories
Terminal blocks
7TB712.9 Accessory terminal block, 12-pin, screw clamps 1.5 mm²
7TB712.91 Accessory terminal block, 12-pin, cage clamp terminal block 1.5 mm²
7TB718.9 Accessory terminal block, 18-pin, screw clamps 1.5 mm²
7TB718.91 Accessory terminal block, 18-pin, cage clamp terminal block 1.5 mm²
Optional Accessories
Automation Studio HW Upgrades Version (Date) Download
V4.0 HW Upgrade (7XX415.50-K02) / 419 KB
Documentation Version (Date) Download
CX / XX Users Manual / 7 MB
Compact I/O User's Manual / 12 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
Makro-/Artikeldaten für EPLAN Version (7XX415.50-K02) / 2 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File STEP 7XX_7CX / 791 KB