  • Especificaciones

  • Información básica

  • Accesorios

  • Descargas

  • Revisiones

  • Número de serie

    Status displayGreen LED (DC OK), threshold value Uout = 21.5 V
    Isolation voltage
    Input - Output4 kV AC (type test)
    2 kV AC (routine test)
    Input - PE2 kV AC (type test)
    2 kV AC (routine test)
    Output - PE500 VDC (type test)
    Connection typeScrew clamp connection
    Connection cross section
    Wire end sleevesFlexible cables require wire end sleeves in order to fulfill EN 60950 / UL 60950
    Flexible0.2 to 2.5 mm² / 24 to 14 AWG
    Inflexible0.2 to 2.5 mm² / 24 to 14 AWG
    Wire stripping length9 mm (input/output)
    Certification
    CEYes
    ULcULus E123528
    Industrial control equipment
    Nominal input voltage100 to 240 VAC
    Input voltageAC 85 to 264 V (wide range), 45 to 65 Hz
    Input currentApprox. 1.65 A (120 VAC)
    Approx. 0.9 A (230 VAC)
    Inrush current limitation<15 A
    I2t1.1 A2s
    Power failure bypass>20 ms (120 VAC)
    >110 ms (230 VAC)
    Switch-on time<1 s
    Power factor (cos φ)0.72
    Discharge current to PE<3.5 mA
    Protective circuitTransient surge protection (varistor)
    Internal fuse3.15 A, slow-blow
    Required line fuse for line protection6 A
    10 A
    16 A (characteristic B)
    Nominal voltage24 VDC ±1%
    Output power120 W
    Setting range for output voltage22.5 to 29.5 VDC
    Output current
    -25 to 55°C5.0 A
    >55°CDerating: 2.5% per °C
    Current limitationApprox. 10 A (short circuit)
    Control deviation<1% (static load change 10 to 90%)
    <2% (dynamic load change 10 to 90%)
    <0.1% (input voltage change ±10%)
    Rise time<2 ms (UOUT (10 to 90%))
    Residual ripple<20 mVSS
    Switching peaks<30 mVSS
    Can be connected in parallelYes, to establish redundancy and increase capacity
    Can be connected in seriesNo
    Max. capacitive loadUnlimited
    Protection against internal overvoltagesYes, limited to <35 VDC
    Protection functionsOutput protected against continuous short circuit, open circuit and overload
    Power back immunityMax. 35 VDC
    Output noise suppressionUnit complies with EN 55011 (Class B)
    Efficiency>89%
    MTBF>500,000 h, in accordance with IEC 61709 (SN 29500)
    Power dissipation
    Rated loadMax. 18 W
    No-load operationMax. 1.1 W
    Mounting orientation
    HorizontalYes
    VerticalNo
    Ventilation/CoolingNormal convection, no fan required
    Protection per EN 60529IP20
    Rated protectionI, with PE connection
    Temperature
    Operation-25 to 70°C (>55°C derating)
    Storage-40 to 85°C
    Transport-40 to 85°C
    Relative humidity
    OperationMax. 95%, non-condensing
    Vibration
    Operation<15 Hz, amplitude ±2.5 mm, in accordance with IEC 60068-2-6
    15 to 150 Hz, 2.3 g, 90 min
    Shock
    Operation15 g in each direction, in accordance with IEC 60068-2-27
    Pollution degree2, in accordance with EN 50178
    Climate category3K3, in accordance with EN 60721
    Housing
    MaterialSheet metal, galvanized
    Side panels: Aluminum
    InstallationEasy rail mounting (DIN rail NS 35, EN 60715)
    Dimensions
    Width40 mm
    Height130 mm
    Depth115 mm
    Weight600 g

0PS1050.1

  • 100 to 240 VAC wide-range input
  • High dielectric strength
  • Can be connected in parallel for increased capacity and redundancy
  • Reliable operation due to long power failure bypass function under full load and high MTBF (>500,000 h)
  • International certification package
  • Wide temperature range from -25 to 70°C
  • Slender design
  • Closed metal housing
-
Product description:
Material number:
0PS1050.1
Description:
24 VDC power supply, 1 phase, 5 A, input 100 to 240 VAC, wide range, top-hat rail installation