Short description
Power supply module 24 VDC power supply module for Compact or Fieldbus CPU, X2X Link power supply and I/O
Interfaces 1x RS232, 1x CAN bus
General information
B&R ID code 0x2018
Status indicators Overload, operating state, module status, RS232, CAN bus
Diagnostics
Module run/error Yes, using status LED and software
CAN bus data transfer Yes, using status LED
RS232 data transfer Yes, using status LED
Overload Yes, using status LED and software
Power consumption for X2X Link power supply 1.42 W
Power consumption
Internal I/O 0.6 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV GL Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
EAC Yes
KC Yes
CPU / X2X Link power supply input
Input voltage 24 VDC -15% / +20%
Input current Max. 0.7 A
Fuse Integrated, cannot be replaced
Reverse polarity protection Yes
CPU / X2X Link power supply output
Nominal output power 7 W
Parallel connection Yes
Redundant operation Yes
Overload characteristics Short circuit protection, temporary overload
Input I/O power supply
Input voltage 24 VDC -15% / +20%
Fuse Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection No
Output I/O power supply
Nominal output voltage 24 VDC
Behavior on short circuit Required line fuse
Permissible contact load 10 A
Interfaces
Interface IF1
Signal RS232
Variant Connection made using 12-pin terminal block X20TB12
Transfer rate Max. 115.2 kbit/s
Interface IF3
Signal CAN bus
Variant Connection made using 12-pin terminal block X20TB12
Transfer rate Max. 1 Mbit/s
Electrical properties
Electrical isolation
CPU/X2X Link supply isolated from CPU/X2X Link power supply

I/O supply not isolated from I/O power supply
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating See section "Derating"
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately
Order 1x Compact CPU base X20BB22 or X20BB27 separately
Order 1x Fieldbus CPU base X20BB3x/4x separately
Spacing 12.5+0.2 mm
Material number:
X20PS9500
Description:
  • Supply for Compact or Fieldbus CPU, X2X Link network and internal I/O power supply
  • Electrical isolation of supply and CPU / X2X Link power supply
  • Redundancy of CPU / X2X Link supply possible by operating multiple supply modules simultaneously
  • RS232 configurable as an online interface
  • CAN bus

The power supply module is used together with an X20 Compact or Fieldbus CPU. It is equipped with a supply for the Compact or Fieldbus CPU, X2X Link network and internal I/O power supply.

Mandatory Accessories
System modules for compact CPUs
X20BB22 X20 compact CPU base, for compact CPU and compact CPU power supply module, base for integrated RS232 interface, X20 connection, X20 locking plates (left and right) X20AC0SL1/X20AC0SR1 included
X20BB27 X20 compact CPU base, for compact CPU and compact CPU power supply module, base for integrated RS232 and CAN bus interface, X20 connection, X20 locking plates (left and right) X20AC0SL1/X20AC0SR1 included
System modules for fieldbus CPUs
X20BB32 X20 fieldbus CPU base, for fieldbus CPU and compact CPU power supply module, base for integrated RS232 interface, Slot for X20 interface module, X20 connection, X20 locking plates (left and right) X20AC0SL1/X20AC0SR1 included
X20BB37 X20 fieldbus CPU base, for fieldbus CPU and compact CPU power supply module, base for integrated RS232 and CAN bus interface, Slot for X20 interface module, X20 connection, X20 locking plates X20AC0SL1/X20AC0SR1 (left and right) included
X20BB42 X20 fieldbus CPU base, for fieldbus CPU and compact CPU power supply module, base for integrated RS232 interface, 2 slots for X20 interface modules, X20 connection, X20 locking plates (left and right) X20AC0SL1/X20AC0SR1 included
X20BB47 X20 fieldbus CPU base, for fieldbus CPU and compact CPU power supply module, base for integrated RS232 and CAN bus interface, 2 slots for X20 interface modules, X20 connection, X20 locking plates (left and right) X20AC0SL1/X20AC0SR1 included
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Automation Studio HW Upgrades Version (Date) Download
V2.7 HW Upgrade (X20PS9500) EXE / 978 KB
V3.0 HW Upgrade (X20PS9500) EXE / 1 MB
V4.0 HW Upgrade (X20PS9500) EXE / 625 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
DNV GL Type Approval Certificate - X20 / Power Panel T30 PDF / 171 KB
E115267 UL CoC X20 PDF / 825 KB
FTZU 09 ATEX 0083X PDF / 697 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Lloyds Register PDF / 579 KB
Documentation Version (Date) Download
Datasheet X20(c)PS9500 PDF / 206 KB
X20 System User´s Manual PDF / 50 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Please choose country and language