Please choose country and language

Short description
I/O module 6 digital outputs 30 VDC / 240 VAC, outputs are single-channel isolated
General information
B&R ID code 0xE22A
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using status LED
Outputs Yes, using status LED
Power consumption
Bus 1 W
Internal I/O -
Additional power dissipation caused by actuators (resistive) [W] +0.36
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV GL Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
KR Yes
EAC Yes
Digital outputs
Variant Relay / Normally open contact
Channels are single-channel isolated
Nominal voltage 30 VDC / 240 VAC
Max. voltage 264 VAC
Switching voltage Max. 110 VDC / 264 VAC
Rated frequency DC / 45 to 63 Hz
Nominal output current 2 A at 30 VDC / 2 A at 240 VAC
Total nominal current 10 A at 30 VDC / 10 A at 240 VAC
Actuator power supply External
Contact resistance Max. 100 mΩ
Switching delay
0 → 1 ≤10 ms
1 → 0 ≤10 ms
Isolation voltages
Channel - Bus Tested at 2300 VAC
Channel - Channel Tested at 750 VAC
Service life
Electrical Min. 120 x 103 ops. (at 2 A / 240 VAC)
Mechanical Min. 2 x 107 ops.
Switching capacity
Minimum 0.05 W DC / 2.4 W AC
Maximum 60 W DC / 480 W AC
Total power of all channels
AC 3000 W
DC 360 W
Protective circuit
Internal None
External
AC RC combination or VDR
DC Inverse diode, RC combination or VDR
Electrical properties
Electrical isolation Channel isolated from bus
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Not permitted
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Up to 100%, condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x X20TB32 terminal block separately,
Order 1x X20cBM12 bus module separately
Spacing 12.5+0.2 mm
Material number:
X20cDO6639
Description:
  • 6 digital outputs
  • Relay module for 240 VAC / 30 VDC
  • Switching current 2 A
  • 6 normally open contacts
  • Single-channel isolated outputs

The module is equipped with 6 relay outputs.

Mandatory Accessories
Bus modules
X20cBM12 X20 bus module, coated, 240 VAC keyed, internal I/O supply continuous
Terminal blocks
X20TB32 X20 terminal block, 12-pin, 240 VAC keyed
Automation Studio HW Upgrades Version (Date) Download
V3.0 HW Upgrade (X20cDO6639) EXE / 820 KB
V4.0 HW Upgrade (X20cDO6639) EXE / 696 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
DNV GL Type Approval Certificate - X20 / Power Panel T30 PDF / 171 KB
E115267 UL CoC X20 PDF / 825 KB
FTZU 09 ATEX 0083X PDF / 697 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Documentation Version (Date) Download
Coated modules PDF / 60 KB
Data sheet X20(c)DO6639 PDF / 199 KB
X20 System User´s Manual PDF / 50 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Please choose country and language

B&R Logo