Please choose country and language

Short description
Bus transmitter X2X Link bus transmitter with supply for I/O
General information
B&R ID code 0xE219
Status indicators X2X bus function, operating status, module status
Diagnostics
Module run/error Yes, using status LED and software
X2X bus function Yes, using status LED
Power consumption
Bus 0.5 W
Internal I/O
As bus transmitter 0.1 W
Additionally as supply module 0.6 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
EAC Yes
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
Input I/O power supply
Input voltage 24 VDC -15% / +20%
Fuse Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection No
Output I/O power supply
Nominal output voltage 24 VDC
Behavior on short circuit Required line fuse
Permissible contact load 10 A
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Up to 100%, condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x X20TB06 or X20TB12 terminal block separately
Order 1x X20cBM11 bus module separately
Spacing 12.5+0.2 mm
Material number:
X20cBT9100
Description:
  • X2X Link bus transmitter
  • For seamless expansion of the system
  • Up to 100 m segment lengths
  • Feed for internal I/O supply
  • Operation only on the slot to the far right

The bus transmitter provides for the seamless expansion of the X20 System. The stations can be up to 100 m away from each other.

The bus transmitter modules may only be operated with a bus module where the internal I/O supply is connected through (e.g. X20BM11).

If the incoming voltage is used for internal I/O supply, then this potential group must not be supplied by any other module. An I/O module with bus module X20BM01 should be used to separate the potential group.

Mandatory Accessories
Bus modules
X20cBM11 X20 bus module, coated, 24 VDC keyed, internal I/O supply continuous
Terminal blocks
X20TB06 X20 terminal block, 6-pin, 24 VDC keyed
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Optional Accessories
X2X Link cable
X67CA0X99.1000 Cable for custom assembly, 100 m
X67CA0X99.5000 Cable for custom assembly, 500 m
Automation Studio HW Upgrades Version (Date) Download
V3.0 HW Upgrade (X20cBT9100) EXE / 2 MB
V4.0 HW Upgrade (X20cBT9100) EXE / 824 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
E115267 UL CoC X20 PDF / 825 KB
FTZU 09 ATEX 0083X PDF / 697 KB
Documentation Version (Date) Download
Coated modules PDF / 60 KB
Data sheet X20(c)BT9100 PDF / 264 KB
X20 System User´s Manual PDF / 50 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Please choose country and language

B&R Logo