Please choose country and language

Short description
Bus controller Modbus TCP/UDP slave
General information
B&R ID code 0xD577
Status indicators Module status, bus function
Diagnostics
Module status Yes, using status LED and software
Bus function Yes, using status LED and software
Power consumption
Bus 2 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV GL Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
EAC Yes
Interfaces
Fieldbus Modbus TCP/UDP slave
Variant 2x shielded RJ45 (switch)
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 10/100 Mbit/s
Transfer
Physical layer 10BASE-T/100BASE-TX
Half-duplex Yes
Full-duplex Yes
Autonegotiation Yes
Auto-MDI/MDIX Yes
Min. cycle time
Fieldbus 1 ms
X2X Link 500 μs
Synchronization between bus systems possible No
Electrical properties
Electrical isolation Modbus isolated from bus and I/O
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Up to 100%, condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x X20TB12 terminal block separately
Order 1x X20cPS9400 power supply module separately
Order 1x X20cBB80 bus base separately
Spacing 37.5 +0.2 mm
Material number:
X20cBC0087
Description:
  • Fieldbus: Modbus/TCP, Modbus/UDP
  • I/O configuration via the fieldbus
  • DHCP-capable
  • Bootp-capable
  • Integrated double switch for efficient cabling
  • Configurable I/O cycle (0.5 to 4 ms)
  • Response time: <1 - 8 ms (depending on the load on the integrated switch)
  • Validity check for command sequences before execution

Established in 1979, the Modbus protocol has approved the use of Ethernet with both Modbus TCP and Modbus/UDP. Today, Modbus TCP is an open Internet draft standard introduced by Schneider Automation to the Internet Engineering Task Force (IETF), the organization responsible for Internet standardization. The Modbus services and object model have been preserved since the original version and left unchanged for use with the TCP/IP transmission medium.

Modbus/UDP differs from Modbus TCP in that it uses connectionless communication via UDP/IP. The advantages of faster and easier communication with UDP/IP also brings with it the disadvantage of requiring error detection and correction in the application layer.

This bus controller makes it possible to connect X2X Link I/O nodes to Modbus via Ethernet. The bus controller can be operated on B&R controllers through the use of Automation Studio or on third-party systems with Modbus TCP or -UDP master functionality.

Only the standard function model (see the respective module description) is supported when the bus controller is used together with multi-function modules it has automatically configured itself.

All other function models are supported when configured accordingly in Automation Studio V4.3 or later.

Automation Studio can be downloaded at no cost from the B&R website www.br-automation.com. The evaluation license is permitted to be used to create complete configurations for fieldbus bus controllers at no cost.

Mandatory Accessories
System modules for bus controllers
X20cBB80 X20 bus base, coated, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end plates (left and right) X20AC0SL1/X20AC0SR1 included
X20cPS9400 X20 power supply module, coated, for bus controller and internal I/O power supply, X2X Link power supply
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Automation Studio HW Upgrades Version (Date) Download
V3.0 HW Upgrade (X20cBC0087) EXE / 428 KB
V4.3 HW Upgrade (X20cBC0087) EXE / 730 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
DNV GL Type Approval Certificate - X20 / Power Panel T30 PDF / 171 KB
E115267 UL CoC X20 PDF / 1 MB
FTZU 09 ATEX 0083X PDF / 697 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Lloyds Register PDF / 579 KB
Documentation Version (Date) Download
Coated modules PDF / 60 KB
Data sheet X20(c)BC0087 PDF / 183 KB
Modbus/TCP Bus Controller User's manual PDF / 4 MB
X20 System User´s Manual PDF / 50 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File STEP/DXF X20BC and X20IF Module ZIP / 1 MB

Please choose country and language