Please choose country and language

Short description
Communication module 1x X2X Link master, 1x CAN bus
General information
B&R ID code 0x1F26
Status indicators Module status, data transfer, terminating resistor
Diagnostics
Module status Yes, using LED status indicator
Data transfer Yes, using LED status indicator
Terminating resistor Yes, using LED status indicator
Power consumption 1.25 (Rev. <E0: 1.51 W)
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
Interfaces
Interface IF1
Fieldbus X2X Link master
Variant 4-pin male multipoint connector
Number of stations Max. 253
Internal bus power supply No
Network topology Line
Distance between 2 stations Max. 100 m
Bus terminating resistor Internal
Interface IF2
Signal CAN bus
Variant 5-pin male multipoint connector
Max. distance 1000 m
Transfer rate Max. 1 Mbit/s
Terminating resistor Integrated in module
Controller SJA 1000
Electrical properties
Electrical isolation PLC isolated from X2X Link (IF1) and CAN (IF2) and interfaces isolated from each other
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block TB704 and 1x terminal block TB2105 separately.
Slot In X20 CPU
Material number:
X20IF2792
Description:
  • X2X Link connection
  • CAN bus connection
  • Integrated terminating resistor

The interface module can be used to expand the X20 CPU for specific applications. It is equipped with both an X2X Link interface and a CAN bus interface.

Mandatory Accessories
Terminal blocks
0TB2105.9010 Accessory terminal block, 5-pin, screw clamps 2.5 mm²
0TB2105.9110 Accessory terminal block, 5-pin, push-in terminal block 2.5 mm²
0TB704.9 Accessory terminal block, 4-pin, screw clamp terminal block 2.5 mm²
0TB704.91 Accessory terminal block, 4-pin, push-in terminal block 2.5 mm²
Automation Studio HW Upgrades Version (Date) Download
V2.6 HW Upgrade (X20IF2792) EXE / 1 MB
V3.0 HW Upgrade (X20IF2792) EXE / 1 MB
V4.0 HW Upgrade (X20IF2792) EXE / 793 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
E115267 UL CoC X20 PDF / 847 KB
FTZU 09 ATEX 0083X PDF / 697 KB
Documentation Version (Date) Download
Datasheet X20IF2792 PDF / 219 KB
X20 System User´s Manual PDF / 50 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X20 Interface module X20IF2792 ZIP / 38 KB
Dimensions PDF X20 Interface Module X20IF2792 PDF / 4 KB

Please choose country and language

B&R Logo