Short description
Bus controller | EtherNet/IP adapter (slave) |
General information
B&R ID code | 0xE67F |
Status indicators | Module status, network status, bus function |
Diagnostics | |
Module status | Yes, using LED status indicator and software |
Bus function | Yes, using LED status indicator and software |
Network status | Yes, using LED status indicator and software |
Power consumption | |
Bus | 2 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
EAC | Yes |
Interfaces
Electrical properties
Electrical isolation | EtherNet/IP isolated from bus and I/O |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Starting temperature | Yes, -40°C |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | Up to 100%, condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |

Material number:
X20cBC0088Description:
- Fieldbus: EtherNet/IP
- Integrated 3-port switch for efficient cabling
- Auto-configuration of I/O modules
- Can be configured by the scanner (master) using configuration assembly
- Web interface
- DHCP-capable
- Configurable I/O cycle (0.5 - 4 ms)
- Minimum fieldbus cycle time (also requested packet interval or RPI): 1 ms

EtherNet/IP is an Ethernet-based fieldbus. EtherNet/IP was developed by Allen-Bradley (Rockwell Automation) and later transferred to the Open DeviceNet Vendor Association (ODVA) as an open standard. In 1998, a working group at ControlNet International developed a procedure for setting the published Common Industrial Protocol to Ethernet. EtherNet/IP was published in March 2000 as an open industrial automation standard based on this procedure.
This bus controller makes it possible to connect X2X Link I/O nodes to EtherNet/IP. The bus controller can be operated via interface module X20IF10D1-1 or by 3rd-party systems with EtherNet/IP scanner functionality.
Mandatory Accessories
System modules for bus controllers
X20cBB80 | X20 bus base, coated, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end plates (left and right) X20AC0SL1/X20AC0SR1 included |
X20cPS9400 | X20 power supply module, coated, for bus controller and internal I/O power supply X2X Link power supply |
Terminal blocks
X20TB12 | X20 terminal block, 12-pin, 24 VDC keyed |
Automation Studio HW Upgrades | Version (Date) | Download |
---|---|---|
V3.0 HW Upgrade (X20cBC0088) | EXE / 2 MB | |
V4.3 HW Upgrade (X20cBC0088) | EXE / 1 MB |
Certificates | Version (Date) | Download |
---|---|---|
244665 CSA HazLoc Certificate of Compliance X20, X67 | PDF / 56 KB | |
E115267 UL CoC X20 | PDF / 847 KB | |
FTZU 09 ATEX 0083X | PDF / 697 KB |
Documentation | Version (Date) | Download |
---|---|---|
Coated modules | PDF / 60 KB | |
Datasheet X20(c)BC0088 | PDF / 182 KB | |
EtherNet/IP Bus Controller User's Manual | PDF / 4 MB | |
X20 System User´s Manual | PDF / 56 MB |
E-CAD (Electro or EPLAN Templates) | Version (Date) | Download |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 161 MB |
M-CAD (Mechan. Templates) | Version (Date) | Download |
---|---|---|
3D File STEP/DXF X20BC and X20IF Module | ZIP / 1 MB |