Please choose country and language

Short description
Communication module 1 SmartWire master for controlling up to 16 slaves
General information
B&R ID code 0xA38D
Status indicators SmartWire bus function, external supply voltage, operating state, module status
Diagnostics
Module run/error Yes, using status LED and software
SmartWire operating state Yes, using status LED and software
U Aux Yes, using status LED
Power output
Internal I/O 6.8 W for supplying external slaves (equal to 16 slaves each with 0.425 W)
Power consumption
Bus 0.01 W
Internal I/O 1.5 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
Interfaces
Interface
Type SmartWire (LIN bus)
Variant Connection made using 12-pin X20TB12 terminal block
Transfer rate 19200 bit/s
SmartWire
Data format 1 start bit, 8 data bits, no parity bit, 1 stop bit
Max. distance 4 m
Configuration button
Internal Integrated in the module on the bottom of the housing.
External Connection via 12-pin terminal block
N.O. contact, not electrically isolated (use potential-free contact)
SWIRE terminal 1 (24 VDC)
Voltage drop for reverse polarity protection at 3 A Max. 0.1 VDC
Voltage range Voltage and supply
Current-carrying capacity Max. 3 A
Short-circuit proof No, only with external fuse
Monitoring 20 VDC < 24 VDC Aux < 29.4 VDC (via firmware)
SWIRE terminal 2
Daisy chain signal 5 VDC, CMOS level
SWIRE terminal 5 (bus level)
Dominant <2 VDC
Recessive >14.85 VDC
SWIRE terminal 6 (17 VDC)
Voltage range Typ. 16.6 VDC (16.3 VDC to 16.8 VDC)
Summation current Max. 400 mA for 16 SmartWire slaves
Short-circuit proof Yes
Monitoring 14.2 VDC < 17 VDC Aux < 17.9 VDC (via firmware)
U-Aux (24 VDC aux supply)
Connection Externally via 12-pin terminal block
Input voltage 24 VDC -15 % / +20 %
Fuse Recommended line fuse: 3 A, slow-blow
Summation current Max. 3 A for 16 SmartWire slaves
Reverse polarity protection Yes
Electrical properties
Electrical isolation
SmartWire isolated from bus

SmartWire power supply (17 VDC) not isolated from I/O power supply
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation 0 to 55°C
Vertical mounting orientation 0 to 50°C
Derating -
Storage -25 to 70°C
Transport -25 to 70°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order SmartWire attachment cable X20CA4S00.00xx separately
Order 1x X20BM11 bus module separately
Pitch 12.5+0.2 mm
Material number:
X20CS1011
Description:
  • X2X SmartWire master for controlling up to 16 SmartWire slaves
  • Simple connection using pre-assembled connection cables
  • Moeller SmartWire modules for Moeller standard switching devices
  • Replaces control circuit wiring
  • Contactor activation
  • Contactor switching status
  • Motor circuit breaker status
  • 24 VDC control voltage via SmartWire connection cable

SmartWire from the company Moeller makes it possible to very easily integrate switching devices such as contactors or motor protection switches in the X20 system without extensive wiring. It replaces the control circuit wiring between the controller and switching devices with pluggable, pre-assembled connection cables.

Although SmartWire is an intelligent connection, this changes almost nothing for the machine programmer. Integration in the X20 system via the interface module cuts down on overall communication. The individual switching devices can simply be viewed as digital inputs and outputs.

Practical applications

SmartWire allows up to 16 switching devices to be connected using pre-assembled cables and attached to the X20 SmartWire interface module. The system can configure itself completely at the push of a button without additional intervention or effort. This replaces the wiring test that was previously necessary.

At the same time, the device configuration is known to the system. If a device is no longer available due to an error or intervention, it will be detected immediately. Once corrected, the system continues to run.

The interface module is designed as a normal electronic module, which means it can be placed anywhere on the remote backplane.

Mandatory Accessories
Bus modules
X20BM11 X20 bus module, 24 VDC keyed, internal I/O supply continuous
X20BM15 X20 bus module, with node number switch, 24 VDC keyed, internal I/O supply continuous
Others
X20CA4S00.0005 SmartWire attachement cable, X20TB12 to SmartWire connector, 0.5 m
X20CA4S00.0015 SmartWire attachement cable, X20TB12 to SmartWire connector, 1.5 m
Automation Studio HW Upgrades Version (Date) Download
V2.6 HW Upgrade (X20CS1011) EXE / 1 MB
V3.0 HW Upgrade (X20CS1011) EXE / 2 MB
V4.0 HW Upgrade (X20CS1011) EXE / 775 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
E115267 UL CoC X20 PDF / 847 KB
FTZU 09 ATEX 0083X PDF / 697 KB
Documentation Version (Date) Download
Data sheet X20CS1011 PDF / 279 KB
X20 System User´s Manual PDF / 56 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Please choose country and language

B&R Logo