Short description
I/O module | 1x HIPERFACE interface |
General information
B&R ID code | 0xAEC7 |
Status indicators | Counting direction, operating status, module status |
Diagnostics | |
Module run/error | Yes, using status LED and software |
Counting direction | Yes, using status LED |
Power consumption | |
Bus | 0.01 W |
Internal I/O | 1.3 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Type of signal lines | Shielded cables must be used for all signal lines |
Certifications | |
CE | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
EAC | Yes |
KC | Yes |
Encoder inputs
Angular position resolution | 13-bit, with a 1 VSS signal |
Encoder monitoring | Yes |
Max. encoder cable length | 10 m |
Sine/Cosine inputs | |
Signal transmission | Differential signals, symmetrical |
Signal frequency | DC up to 200 kHz |
Differential voltage | 1 VSS |
Common-mode voltage | Max. ±10 V |
Terminating resistor | 120 Ω |
Encoder power supply
Output voltage | 11 V |
Load capacity | 150 mA |
Protective measures | |
Overload-proof | Yes |
Short-circuit proof | Yes |
Parameter channel (RS485)
Signal transmission | 5 VDC differential signal, EiA RS-485 standard |
Transmission status | See HIPERFACE specification |
Electrical properties
Electrical isolation |
Channel isolated from bus Channel not isolated from channel
|
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitations |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section "Derating" |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x X20TB12 terminal block separately Order 1x X20BM11 bus module separately |
Pitch | 12.5+0.2 mm |

Materialenummer:
X20DS1828Beskrivelse:
- HIPERFACE encoder interface
- Encoder input monitoring
- 11 VDC and GND for encoder supply
- NetTime timestamp: Position time
The module is equipped with 1 HIPERFACE encoder interface. This module can be used to evaluate encoders installed in motors from other manufacturers as well as encoders for external axes (encoders that sample any machine movement). The input signals are monitored. This makes it possible to detect open or shorted lines as well as encoder supply failures.
Obligatoriske tilbehør
Automation Studio HW Upgrades | Version (Date) | Download |
---|---|---|
V2.7 HW Upgrade (X20DS1828) | EXE / 2 MB | |
V3.0 HW Upgrade (X20DS1828) | EXE / 6 MB | |
V4.0 HW Upgrade (X20DS1828) | EXE / 3 MB |
Certifikater | Version (Date) | Download |
---|---|---|
244665 CSA HazLoc Certificate of Compliance X20, X67 | PDF / 56 KB | |
E115267 UL CoC X20 | PDF / 847 KB | |
FTZU 09 ATEX 0083X | PDF / 697 KB | |
X20, X67 KC certificates | PDF / 6 MB |
Dokumentation | Version (Date) | Download |
---|---|---|
Datasheet X20DS1828 | PDF / 1 MB | |
X20 System User´s Manual | PDF / 56 MB |
E-CAD (Electro eller EPLAN Templates) | Version (Date) | Download |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 177 MB |
M-CAD (Mechan. Templates) | Version (Date) | Download |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 KB | |
3D File STEP X20 I/O-Slice | ZIP / 872 KB | |
Dimensions PDF X20 Electronic module | PDF / 3 KB |