Short description
Bus controller EtherNet/IP adapter (slave)
General information
B&R ID code 0x26D8
Status indicators Module status, network status, bus function
Diagnostics
Module status Yes, using status LED and software
Bus function Yes, using status LED and software
Network status Yes, using status LED and software
Power consumption
Bus 2 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
Interfaces
Fieldbus EtherNet/IP adapter (slave)
Variant 2x shielded RJ45 (switch)
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 10/100 Mbit/s
Transfer
Physical layer 10BASE-T/100BASE-TX
Half-duplex Yes
Full-duplex Yes
Autonegotiation Yes
Auto-MDI/MDIX Yes
Min. cycle time
Fieldbus 1 ms
X2X Link 500 μs
Synchronization between bus systems possible No
Electrical properties
Electrical isolation EtherNet/IP isolated from bus and I/O
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x X20TB12 terminal block separately
Order 1x X20PS9400 or X20PS9402 power supply module separately
Order 1x X20BB80 bus base separately
Spacing 37.5 +0.2 mm
Materialenummer:
X20BC0088
Beskrivelse:
  • Fieldbus: EtherNet/IP
  • Integrated 3-port switch for efficient cabling
  • Auto-configuration of I/O modules
  • Can be configured by the scanner (master) using configuration assembly
  • Web interface
  • DHCP-capable
  • Configurable I/O cycle (0.5 - 4 ms)
  • Minimum fieldbus cycle time (also requested packet interval or RPI): 1 ms

EtherNet/IP is an Ethernet-based fieldbus. EtherNet/IP was developed by Allen-Bradley (Rockwell Automation) and later transferred to the Open DeviceNet Vendor Association (ODVA) as an open standard. In 1998, a working group at ControlNet International developed a procedure for setting the published Common Industrial Protocol to Ethernet. EtherNet/IP was published in March 2000 as an open industrial automation standard based on this procedure.

This bus controller makes it possible to connect X2X Link I/O nodes to EtherNet/IP. The bus controller can be operated via interface module X20IF10D1-1 or by 3rd-party systems with EtherNet/IP scanner functionality.

Obligatoriske tilbehør
System modules for bus controllers
X20BB80 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end plates (left and right) X20AC0SL1/X20AC0SR1 included
X20PS9400 X20 power supply module, for bus controller and internal I/O power supply, X2X Link power supply
X20PS9402 X20 power supply module, for bus controller and internal I/O power supply, X2X Link power supply, supply not electrically isolated
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Automation Studio HW Upgrades Version (Date) Download
V3.0 HW Upgrade (X20BC0088) EXE / 1 MB
V4.3 HW Upgrade (X20BC0088) EXE / 733 KB
Certifikater Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
Declaration of Conformity X20BC0088 PDF / 55 KB
E115267 UL CoC X20 PDF / 1 MB
FTZU 09 ATEX 0083X PDF / 697 KB
Dokumentation Version (Date) Download
Datasheet X20(c)BC0088 PDF / 182 KB
EtherNet/IP Bus Controller User's Manual PDF / 4 MB
X20 System User´s Manual PDF / 50 MB
E-CAD (Electro eller EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File STEP/DXF X20BC and X20IF Module ZIP / 1 MB

Vælg venligst land og sprog