Produkty
Specifikace
Základní informace
Příslušenství
Ke stažení
Revize
Sériové číslo
Communication module1x CAN bus, 1x X2X Link master
Ready relayNormally open and normally closed contact, max. 30 VDC, max. 6 A
Status indicators1 LED per interface for sending data
Diagnostics
Data transferYes, using LED status indicators and software
Power consumption2.28 W
Electrical isolation
IF1 - IF2Yes
PC - IFxYes
Certification
CEYes
ULcULus E115267
Industrial control equipment
Industrial control equipment
GOST-RYes
SRAM1 MB, battery-backed
IF1 interface
SignalCAN bus
This CAN bus interface can be configured as a CANopen master in Automation Studio 3.0 and higher.
Design4-pin male multipoint connector
Max. distance1000 m
Transfer rateMax. 500 kbit/s
IF2 interface
FieldbusX2X Link master
Design4-pin male multipoint connector
Distance between 2 stationsMax. 100 m
EN 60529 protectionIP20 when installed
Temperature
Operation0 to 60°C
Storage-25 to 70°C
Relative humidity
Operation5 to 95%, non-condensing
NoteOrder 3x 0TB704.9 terminal blocks separately
Lithium battery included in delivery
Lithium battery included in delivery
SlotStandard PCI half-size module, Plug & Play
Installation in
B&R Automation PCYes
B&R Panel PCYes
Desktop PCYes

Product description:
Material number:
5LS197.6
Description:
Logic scanner, PCI half-size module, 1 X2X Link master interface, electrically isolated, 1 CAN interface, electrically isolated, max. 500 Mbit/s, object buffer in transmit and receive direction, 1 MB SRAM (Automation Runtime), order 3x 0TB704.9 terminal blocks separately
Terminal blocks
- 0TB704.9
Accessory terminal block, 4-pin, screw clamps 2.5 mm²
Batteries
- 0AC201.91
Lithium batteries 4 pcs., 3 V / 950 mAh button cell
- 4A0006.00-000
Lithium battery, 3 V / 950 mAh, button cell
Infrastructure components
- 0AC913.93
Bus adapter, CAN bus, 2 CAN bus interfaces, including 03 m attachment cable (TB704)
zobrazit vše